Fujitsu AUXG09KVLA Design & Technical Manual page 65

Hide thumbs Also See for AUXG09KVLA:
Table of Contents

Advertisement

 Outdoor units installation in multi-row
Single parallel unit arrangement
NOTES:
• If the space is larger than stated above, the condition will be the same as when there is no ob-
stacle.
• When installing the outdoor unit, be sure to open the front and left side to obtain better operation
efficiency.
CAUTION
• Do not install the outdoor unit in two-stage where the drain water could freeze. Otherwise the
drainage from the upper unit may form ice and cause a malfunction of the lower unit.
• When the outdoor temperature is 0 °C or less, do not use the accessory drain pipe and drain
cap. If the drain pipe and drain cap are used, the drain water in the pipe may freeze in extremely
cold climate. (For reverse cycle model only.)
• In area with heavy snowfall, if the inlet and outlet of the outdoor unit is blocked with snow, it
might become difficult to get warm, and it is likely to cause product malfunction. Construct a
canopy and a pedestal, or place the unit on a high stand that is locally installed.
3-1. Models: AOYG09KATA, AOYG12KATA, AOYG14KATA, AOYG18KATA, and
AOYG22KATA
100 or more
1,000 or more
200 or more
500 or more
Multiple parallel unit arrangement
250 or more
1,000 or more
- 59 -
Unit: mm
200 or more
2,000 or more
400 or more
1,000 or more
200 or more
200 or more
3. Installation space