Capacity Compensation Rate For Pipe Length And Height Difference; Model: Aoyg09Kata - Fujitsu AUXG09KVLA Design & Technical Manual

Hide thumbs Also See for AUXG09KVLA:
Table of Contents

Advertisement

6. Capacity compensation rate for pipe length and height
difference
Indoor unit is higher than outdoor unit
Indoor unit
Connection pipe

6-1. Model: AOYG09KATA

NOTE: Values mentioned in the table are calculated based on the maximum capacity.
Indoor unit is higher than outdoor
Indoor unit is lower than outdoor
Indoor unit is higher than outdoor
Indoor unit is lower than outdoor
6-1. Model: AOYG09KATA
Height difference H
H
Outdoor unit
COOLING
1
unit *
2
unit *
HEATING
1
unit *
2
unit *
1
Indoor unit is lower than outdoor unit
*
Outdoor unit
Connection pipe
5
15
10
7.5
5
0.992
0
1.000
-5
1.000
-7.5
-10
-15
5
15
10
7.5
5
1.000
0
1.000
-5
0.995
-7.5
-10
-15
- 65 -

6. Capacity compensation rate for pipe length and height difference

2
*
H
Indoor unit
Pipe length (m)
7.5
10
0.964
0.988
0.968
0.992
0.972
1.000
0.980
1.000
0.980
1.000
0.980
0.980
Pipe length (m)
7.5
10
1.010
1.000
1.010
1.000
1.010
1.000
1.010
0.995
1.005
0.993
1.002
0.999
15
0.903
0.918
0.922
0.925
0.933
0.933
0.933
0.933
0.933
15
0.943
0.943
0.943
0.943
0.943
0.939
0.936
0.934
0.925