Chapter 6 Troubleshooting - Siemens Sm@rt DAS User Manual

Table of Contents

Advertisement

Chapter 5
Troubleshooting
DAS is not turning on
Verify Switch to Controller Wiring
 Locate the Sm@rt DAS controller in the gear. When the
switch is closed, one of the green LED highlighted in red
will turn on indicating the 24V signal gets to the PLC. If
the light does not come on, check wiring from PLC to
switch and from switch to 24V power supply. Ensure
wires were connected between any shipping splits.
Verify Controller to Indicator Light Wiring
 The corresponding green LED highlighted in blue on the
controller indicates the breaker is in maintenance mode.
If this light is green and the blue light does not come on,
check output wires from the controller to the light and
from the light to the power supply. Ensure wires were
connected between any shipping splits.
Verify Communication Modules have power
 Check each communication module and verify each has
green LEDs on indicating power as per commissioning
requirements. If not, verify power connection wiring.
Power LEDs
22
Verify device is communicating
 Each device will have a MODBUS communication light –
verify that it is green as well when the switch is closed.
Check wiring to ensure all connections are made,
especially across shipping splits.
Verify VL settings
 Ensure VL breaker nominal settings are at or higher than
maintenance mode instantaneous settings, and that
instantaneous settings are turned on.
Additional support
 Review the FAQ document for additional support topics.
It is available through the Siemens Download Center.
 Support, service, parts and repairs are available seven
days a week, 24 hours a day, 365 days a year. Call
Siemens Industry Customer Care Center (ICCC) at
800-333-7421.
Input LEDs
Output LEDs

Advertisement

Table of Contents
loading

Table of Contents