Siemens UH50 Series Manual page 32

Ultrasonic heat and cooling energy meters
Table of Contents

Advertisement

Power supply optional
Standard battery
WZU-BA+GUM
- Universal battery
WZU-BDS
- Power pack
AC 230 V
WZU-AC230-15
WZU-AC230-50
WZU-AC230-100
- Power pack
AC/DC 24 V
WZU-ACDC24-00
Communication
- Pulse module
WZU-P2/WZU-P2L
32 / 40
Siemens
Building Technologies
Standard battery
-
Battery type
-
Battery voltage
-
Battery life
Universal battery
Battery type
Battery voltage
Battery life
Power pack AC 230 V
-
Safety class
-
Voltage range
-
Frequency
-
Max. power consumption
-
Overvoltage category II
as per EN 61010-1
-
Length of connecting cable
-
External fusing of supply line
-
Backup in the event of a
power failure
Power pack AC/DC 24 V
-
Safety class
-
Voltage range
-
Frequency
-
Max. power consumption
-
Terminals
-
For connecting line
-
Backup in the event of a
power failure
Pulse outputs
-
Number of outputs per module
-
Standard pulses
-
Pulse valencies
-
Pulse duration
-
Period duration
-
Pulse for operating states
-
Pulse duration for "Ready"
-
Pulse duration for "Fault"
-
Period duration
-
Fast pulses
-
Pulse duration
-
Max. pulse frequency
-
Fast pulses
-
Pulse duration
-
Max. pulse frequency
Ultrasonic heat and cooling energy meters UH50..
2 AA lithium batteries (Li-SOCI2)
3.6 V
Up to 6 years
1 D-cell lithium battery (Li-SOCI2)
3.6 V
6...16 years (depending on configuration)
II
AC 196...253 V
50/60 Hz
0.8 VA
2,500 V surge voltage
1.5 m/5 m/10 m
Automatic cutout 6 A
>20 minutes
III (SELV)
AC 12...36 V or DC 12...42 V
50/60 Hz or DC
0.8 VA
2x1.5 mm²,
Ø 5.0...6.0 mm
>20 minutes
2
For energy, volume and tariff register
1 kWh, 10 kWh, 1 MJ, 10 MJ, 100 MJ,
3
3
0.1 m
, 1 m
per pulse
100 ms conducting
>200 ms
0.1...0.25 ms conducting
Constantly non-conducting
500 ms
If 1 pulse module is fitted
2...100 ms in increments of 1 ms
33 Hz
If 2 pulse modules are fitted
5...100 ms in increments of 5 ms
33 Hz
CE2N5324en
2013-01-14

Hide quick links:

Advertisement

Table of Contents
loading