8. Motor and Application Specific Settings

It is essential that before running the motor, the motor nameplate data matches the motor data in the inverter.

8.1 Set Motor Nameplate Data (02-01, 02-05)

02-05 Motor Rated Power
The nominal motor rated capacity is set at the factory. Please verify that the motor name plate data matches the
motor rated capacity shown in parameter 02-05. The setting should only be changed when driving a motor with a
different capacity.
Range: 0.1 to 37.0 kW (1HP = 0.746 kW)
To set parameter 02-05:
- After power-up press the DSP/FUN key
- Select 02 Motor Parameter
- Press READ/ ENTER key
- Select parameter -01 with the UP/DOWN ▲ and ▼ keys and press the READ/ ENTER key.
Default values vary based on the inverter model.
02-01 Motor Rated Current
The motor rated current is set at the factory based on the inverter model. Enter the motor rated current from the
motor nameplate if it does not match the value shown in parameter 02-01.
Setting range: 0.2 to 100.00A
To set parameter 02-01:
- After power-up press the DSP/FUN key
- Select 02 Motor Parameter
- Press READ/ ENTER key
- Select parameter -01 with the UP/DOWN ▲ and ▼ keys and press the READ/ ENTER key.
8-1