POWER INPUTS
POWER INPUTS
MOTOR INPUTS
MOTOR INPUTS
HIGH VOLTAGE CONNECTIONS
POWER INPUTS:
POWER INPUTS:
JP1
JUMPER ON (MOM)
WITH THE JUMPER ON, THE RUN TIMER IS OFF AND THE
SMC WILL DRIVE THE MOTOR ONLY AS LONG AS THE UP
OR DOWN BUTTON IS PRESSED
NOTES:
1) THE REVERSING DETECTOR CONTROLS ARE
DEACTIVATED IN THIS MODE.
2) THE SEQUENCING CONTROL IS DEACTIVATED IN THIS
MODE.
3) THIS MODE CAN BE USED TO CLOSE THE DOOR IF
THERE IS A MALFUNCTION IN THE REVERSING
DETECTORS. THIS MUST ONLY BE DONE IF THE
UP/DOWN SWITCH IS IN DIRECT VIEW OF THE DOOR.
THE REVERSING DETECTORS MUST BE SERVICED AS
SOON AS POSSIBLE AND THE DOOR RETURNED TO ITS
NORMAL OPERATING MODE.
6100 BROKEN SOUND PKWY. N.W., #14
BOCA RATON, FL 33487
PHONE: 800-822-7468
G - GROUND
N - 120 VAC NEUTRAL
L - 120VAC HOT
JUMPERS
RUN TIME JUMPER JP1 (TOP)
SIMU U.S.INC
FAX: 561-995-7502
POWER
POWER
JP1
STOP
SAFETY
MOTOR INPUTS:
MOTOR INPUTS:
*IF MOTOR RUNS IN WRONG DIRECTION, REVERSE
THE RED AND BLACK MOTOR WIRES
JP1
WITH THE JUMPER OFF, THE RUN TIMER IS ACTIVE AND
THE SMC WILL DRIVE THE MOTOR FOR 1 MINUTE (OR
TO THE MOTOR LIMIT) WHEN THE UP OR DOWN BUTTON
IS PRESSED. PRESSING THE OTHER DIRECTION WHEN THE
MOTOR IS RUNNING WILL CAUSE THE MOTOR TO STOP
FOR 1/4 SECOND BEFORE REVERSING DIRECTIONS.
.
NOTES:
1) THE SMC MUST BE IN THIS MODE FOR THE
SEQUENCING AND REVERSING DETECTORS TO BE
ACTIVE.
INSTALLERS MANUAL
PAGE: 1 OF 5
+
G - MOTOR GROUND (GREEN)
N - MOTOR NEUTRAL (WHITE)
U - MOTOR UP (BLACK*)
D - MOTOR DOWN (RED*)
JUMPER OFF (CONT)