3 Specifications
3 Specifications
Environmental
-25°C to +65°C
Ambient Humidity: 0 to 95% non-condensing
Software
Configuration: MasterLink R510+ (Windows, IOS, Android)
Data Collection: TDS, PowerSpring, DC2009, Itron MV90, and other third-party software
providers
Data Inputs
Max frequency: 3Hz - 50% duty cycle, 10 Hz – 40% duty cycle
Memory
1 year+ of hourly/10 user-specified log items
Pulse Input Circuit
Full temperature range
Max wetting current provided = 35 microamps
Max transmitter leakage current - 7 microamps
Max Pulser + Line Resistance = 200 ohms
Max line length = 300 feet
Parameter
LTE Connectivity
Receiver Input Sensitivity@
ARP (ch.bandwidth 5MHz)
Conditions
Band 2, 4, 5, 13 and 17
LTE 700 Band 17
LTE 700 Band 13
LTE 850 Band 5
LTE AWS Band 4
LTE 1900 Band 2
Min.
Typical
-97
-102
-98
-103
-98
-104
-100
-103
-98
-103
Unit
dBm
dBm
dBm
dBm
dBm