Restore The Original Serial Cable Connection - Honeywell CNI4 Operating And Installation Manual

Table of Contents

Advertisement

7 Getting Started
6. Navigate to View/Edit > Configure by Group > Radio Configuration, and set the following
parameters.
Item
No.
3071 Verizon enable
3016 Fetch Radio Parameters
3021 ModemIPType
Packet service Connection
3022
command
3064 Manual APN Enable
3023 APN Name
7. Cloud Link must be externally powered and modem session timeout must be configured to 180
seconds if MiWireless mode is enabled.
Item No.
3142
MiWireless Enable
3028
Modem session timeout
8. Disconnect MasterLink.
9. Power cycle the CNI4.

7.8 Restore the original serial cable connection

To restore the original serial cable connection
1. Disconnect the USB to serial cable.
2. Restore the original serial interface between the Pulse Accumulator and the Cloud Link 4G Modem.
Description
1 = Enable
1 = Set
2 = IPv6
ATD*99***3#
1 = Enable
Provided By Verizon
Description
Verizon
Recommended Value
1 = Enable
180 seconds
Non-Verizon
0 = Disable
1 = Set
0 = IPv4
ATD*99#
1 = Enable
Example for AT&T:
12221.mcs
Honeywell
| 22

Advertisement

Table of Contents