7 Getting Started
8. Navigate to View/Edit > Configure by Group > Site Information and change the Site ID to the value
required by MDM software.
9. Navigate to View/Edit > Configure by Group > Modem Call-in Configuration, and set the following
(Honeywell default) parameters. 
Item No.
333
Call-in Trigger
449
Switch Filtering
486
Modem AT-Command Enable
334
Scheduled Call-In Date
335
Scheduled Call-In Time
336
Call-In Retry By
339
Scheduled Call-In Phone number
485
Call-Out Stop Time
490
Call-Out Start Time
493
Alarm Call-In Phone number
495
Modem Retry Interval A
496
Modem Retry Interval B
497
Modem Retry A Count
10. Click Disconnect to disconnect MasterLink from the Pulse Accumulator. On successful
disconnection from the Pulse Accumulator, a status message is displayed. Close the pop-up to
acknowledge the message.
Description
Recommended Value
3 = Alarm & Scheduled Call-in
1 = Filter Both Channels
1-yes
Set to the desired call-in date
Set to the desired call-in time
Instrument
<IP>/<Port>Example:
192.168.1.1/50467
00:00:00
00:00:00
<IP>/<Port> Example:
192.168.1.1/50467
5 minutes
1440 minutes
3
Honeywell
| 20