Adjust Menu - Rehau PD1 Instructions Manual

Table of Contents

Advertisement

Adjust Menu

(1 of 6) – Installer access level
Notes:
1- DIP switch must be set to allow access.
2- Press the MENU button to access. Press ^ or v to change
3- Depending on the HEAT, COOL or AUTO option selected, the sequence of illustrated below will differ.
Mode
Current mode of operation the thermostat.
OFF, HEAT
OFF, COOL, AUTO, HEAT
Room Heat (No Schedule)
Desired temperature for heating. (Must have an active air sensor
and be set to either Heat or Auto.)
Room Cool (No Schedule)
Desired temperature for cooling.
(Must have an active air sensor and be set to either Cool or Auto.)
35 to 100° F (1.5 to 38.0° C)
Slab Minimum (No Schedule)
(Must have an active air sensor and be set to either Heat or Auto).
OFF, 34 to 122°F (OFF, 1.0 to 50.0° C)
Room Heat Wake
Desired room temperature at wake-up.
(Must have an active air sensor and be set to either Heat or Auto).
35 to 100° F (1.5 to 38.0° C)
Page 9 of 19
(PD1)
(PD2)
35 to 100° F (1.5 to 38.0° C)
Minimum desired slab temperature.
NOTE: wake, un-occupied, occupied and
sleep times are inputted in the "schd" menu.