Model PWS-70P-DMX

Model #PWS-70P-DMX is designed for new applications where CAT5/5e or CAT6 can be provided or retrofit
applications where existing Belden #9773 exists. Capable of up to 70 presets, this model will accept DMX512
on its input and output DMX512 when configured as a room Main Station. Inter-room communication between
multiple PWS will be PMX multiplex (RS485) protocol.
Model PWS-70P-DMX Configuration and DIP Switch Settings
Important!
One station in each LAN must be designated as a Main PWS (switch 4 ON). Only one Main Station per
LAN. All Secondary PWS connected to the Main PWS (maximum 14 PWS) must have switch 4 turned OFF.
Important!
Communication between Main PWS and Secondary PWS is PMX protocol (Presidor™ Multiplex).
This RS485 protocol requires active termination (switch 2 ON) on the first and the last PWS in the LAN for each
room/zone.