Overview
The Voltage Output Analog Current Sensors are designed for use in any AC current
monitoring application in which you are looking to monitor a particular piece of
equipment for proper operation. All voltage output current sensors use an "Average"
current measuring method and should be used in applications where a pure
Sinusoidal AC waveform that has very little or no distortion/noise on the conductor
being monitored. Applications may include monitoring a resistive type load such as an
incandescent light bulb or heating element as well as any single speed linear load.
Voltage Output current sensors are available in both solid and split-core versions
which also includes a Patented 35 mm Din Rail mounting foot for easy installation in
panel mount applications. The solid-core versions are a great choice for new
installations or OEM applications in which cost sensitivity, lower trip points and
environmental issues like dust and moisture may be of concern. The split-core version
of the current sensors work great in retro-t applications and for use on service technicians vehicles since one or two parts
will work in most applications and can be easily installed without disconnecting any wires. For best results, the voltage
output current sensors should not be used in applications with switching power supplies or variable speed drives due to
the limited operating frequency range. In applications where variable speed drives or waveforms include distortion/noise,
Carrier recommends the use of the NSA-A/CTA2-RMS or NSA-A/SCTA2-RMS Series sensors where you need to supply
24 VDC power to the current sensors with a 4-20 mA signal. A 249 Ohm or 499 Ohm 1 Watt resistor can be used to
convert the 4-20 mA signal into a useable 1-5 or 2-10 VDC output signal at your building management system or PLC.
Applications: Load Trending, Single Speed Loads, Pumps, Compressors, Fans, Preventative Maintenance, LEED,
Project Justification (Calculating ROI), Process Control
Part Numbers
NSA-A/SCTE2-50
NSA-A/SCTV2-150
Specifications
Monitored Current Type:
Maximum AC Voltage:
Isolation Voltage:
Operating Frequency Range:
Core Style:
Supply Voltage:
Sensor Amperage Range:
Output Signal | Number of Wires:
1
Accuracy
:
Response Time:
Aperture Size:
Din Rail Size:
Operating Temperature Range:
Operating Humidity Range:
Recommended Storage Temp | RH Range:
Enclosure Material | Flammability Rating:
Wiring Connections:
Wire Recommendations:
Catalog No. 11-808-790-01
NSA-A/SCTE2-150
NSA-A/SCTV2-250
AC Current
600 VAC
2200 VAC
50 to 600 Hz
NSA-A/SCTE2 Series: Split | NSA-A/SCTV2 Series: Solid
Induced from the Monitored Conductor (Insulated Conductors only)
NSA-A/SCTx2-50: 50 | NSA-A/SCTx2-150: 150 | NSA-A/SCTx2-250: 250
NSA-A/SCTE2 Series: 0 to 5 VDC | NSA-A/SCTV2 Series: 0 to 10 VDC | 2-Wires
NSA-A/SCTE2 Series (0-10A Range Only): +/- 1% from 5-100% of Selected Range
NSA-A/SCTE2 Series (All Other Ranges): +/- 1% from 2-100% of Selected Range
NSA-A/SCTV2 Series: +/- 1% from 5-100% of Selected Range
< 300 mS (Rise and Fall Times)
0.75" (19.05 mm)
35 mm (U.S. Patent No. 7,416,421)
5 to 104ºF (-15 to 40ºC)
0 to 95%, non-condensing
41 to 95ºF (5 to 35ºC) | 40% to 85% RH, non-condensing
PC/ABS (Polycarbonate/ABS Blend) | UL94-V0
2 Position, Screw Terminal Block (Polarity Sensitive)
2 Conductor (Shielded Cable)
Specifications subject to change without notice.
Voltage Output Analog Current Sensors
NSA-A/SCTE2-250
Installation and Operation
NSA-A/SCTV2-50
Page 1 of 5

Advertisement

loading

Summary of Contents for Carrier NSA-A/SCTE2-50

  • Page 1 In applications where variable speed drives or waveforms include distortion/noise, Carrier recommends the use of the NSA-A/CTA2-RMS or NSA-A/SCTA2-RMS Series sensors where you need to supply 24 VDC power to the current sensors with a 4-20 mA signal. A 249 Ohm or 499 Ohm 1 Watt resistor can be used to convert the 4-20 mA signal into a useable 1-5 or 2-10 VDC output signal at your building management system or PLC.
  • Page 2: Dimensional Drawing

    Voltage Output Analog Current Sensors Installation and Operation #NSA-A/SCTE2-50, NSA-A/SCTE2-150, NSA-A/SCTE2-250, NSA-A/SCTV2-50, NSA-A/SCTV2-150, NSA-A/SCTV2-250 11/14/2019 Wire Size: 18 to 24 AWG (0.823 mm to 0.205 mm ) Copper Wires only Terminal Block Torque Rating: 4.43 to 5.31 in-lbs. (0.5 to 0.6 Nm) 1”...
  • Page 3: Installation

    Voltage Output Analog Current Sensors Installation and Operation #NSA-A/SCTE2-50, NSA-A/SCTE2-150, NSA-A/SCTE2-250, NSA-A/SCTV2-50, NSA-A/SCTV2-150, NSA-A/SCTV2-250 11/14/2019 Installation Precautions  This product is not intended to be used for Life or Safety applications.  This product is not intended for use in any hazardous or classified locations.
  • Page 4: Wiring Instructions

    Figure 4 Carrier recommends the use of a two conductor 16 to 22 AWG shielded cable, copper wire only, for all Analog current sensor installations. A maximum wire length of less than 30 meters (98.4 feet) should be used between the current sensors and the Building Management System or controller.
  • Page 5: Troubleshooting

    Voltage Output Analog Current Sensors Installation and Operation #NSA-A/SCTE2-50, NSA-A/SCTE2-150, NSA-A/SCTE2-250, NSA-A/SCTV2-50, NSA-A/SCTV2-150, NSA-A/SCTV2-250 11/14/2019 Troubleshooting Problem Solution No reading  Verify that there is current -owing through the conductor being monitored with a clamp-on current probe. The power for the current sensor is induced from the conductor being monitored.