Siemens RDF270 Manual page 15

Fresh air fan controller with touch buttons
Table of Contents

Advertisement

Application setup based on selection of Fresh Air Unit or Equipment
Settings of these parameters, P02, P24 and P25 determine the RDF270 functionalities:
Available function & user adjustment
Factory settings
1
0
0
Operating mode (
Fan speed: 1, 2, 3
Air circulation mode is fixed:
1. External without BYPASS only
1
1
0
Operating mode (
Fan speed: 1, 2, 3
Air circulation mode via manual selection:
1. External without BYPASS
2. External with BYPASS
1
0
1
Operating mode (
Fan speed: 1, 2, 3
Air circulation mode via manual selection:
1. External without BYPASS
2. Internal
1
1
1
Operating mode (
Fan speed: 1, 2, 3
Air circulation mode via manual selection:
1. External without BYPASS
2. External with BYPASS
3. Internal
2
0
0
Operating mode (
Fan speed: 1, 2, 3
Air circulation mode is fixed:
1. External without BYPASS
Siemens
Smart Infrastructure
): ON, OFF
): ON, OFF
): ON, OFF
): ON, OFF
): ON, OFF (since P25 = 0)
Typical applications /
equipment
Single duct fresh air
unit (FAU)
Dual duct FAU only
Single duct fresh air unit
(FAU)
15
A6V12068497_en--_a
2021-04-16