Arthur Grillo DPC310 Installation And Operation Manual

Arthur Grillo DPC310 Installation And Operation Manual

Differential pressure controller

Advertisement

Quick Links

Installation and operation manual
DPC310
-
DIFFERENTIAL PRESSURE CONTROLLER
Low pressure multi range sensor
with PI-control mode and multifunctional input and output
Doc.-no.: DPC310_01_EN
Issue: 01/2018

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the DPC310 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Arthur Grillo DPC310

  • Page 1 Installation and operation manual DPC310 DIFFERENTIAL PRESSURE CONTROLLER Low pressure multi range sensor with PI-control mode and multifunctional input and output Doc.-no.: DPC310_01_EN Issue: 01/2018...
  • Page 2 Arthur Grillo GmbH. This applies in particular to duplications, trans- lations, microfilming and storage and processing in electronic systems.
  • Page 3: Table Of Contents

    Dimensions Wall mounting Start up Overview DPC310 Electrical connection Schematic view inside Pressure connections Schematic view inside Zero adjustment Operation How to configure the DPC310 5.1.1 Measuring mode 5.1.2 Control mode Adjustable parameters Threshold calculation Function alarm output 5.4.1 Control mode 5.4.2...
  • Page 4: General Safety Instructions

    GENERAL SAFETY INSTRUCTIONS General safety instructions 1.1 Signal words for safety instructions The safety instructions in this operation manual are designed to prevent hazards. They can be found in the operation manual before an operation / task / activity is described, which can entail a possible hazard.
  • Page 5: Product Description

    An additional limit switch with several options can also be used if required. Besides the measuring mode the DPC310 also can be operated in a control mode. Two setpoints can be set and selected via the potential free contact input. The PI-Al- gorithm matches the measured differential pressure by the setpoint and manages the control variable so that a constant pressure results.
  • Page 6: Installation

    INSTALLATION Installation The differential pressure controller DPC310 is designed for wall mounting. • The mounting surface must be solid enough and vibration-free. • The environment has to fulfil the ambient climatic conditions as given in the technical data. CAUTION Material damage...
  • Page 7: Start Up

    START UP Start up 4.1 Overview DPC310 Front cover Cable gland Pressure connection 1 Pressure connection 2 Cable gland Elektrischer Anschluss 4.2 Electrical connection DPC310 + 10...30 Vdc or 24 Vac (±15%) electronic excitation - GND + 0...10 Vdc output ΔP...
  • Page 8: Schematic View Inside

    Doc.-no.: DPC310_01_EN Issue: 01/2018...
  • Page 9: Measuring Mode

    Doc.-no.: DPC310_01_EN Issue: 01/2018...
  • Page 10: Operation

    OPERATION Doc.-no.: DPC310_01_EN Issue: 01/2018...
  • Page 11 OPERATION Doc.-no.: DPC310_01_EN Issue: 01/2018...
  • Page 12 OPERATION Doc.-no.: DPC310_01_EN Issue: 01/2018...
  • Page 13: Control Mode

    Parameter Selection or parameter range Default setting Unit Pa and m³/h or InH20 and cfm Pa and m³/h DPC310-200 (Part-no: 2542) 0...200 Pa, 0...150 Pa, 0...100 Pa, 0...50 Pa 0...200 Pa Measuring DPC310-1000 (Part-no: 2543) range: 0...1000 Pa, 0...750 Pa, 0...500 Pa, 0...250 Pa 0...1000 Pa...
  • Page 14: Threshold Calculation

    DPC310 (0...1000 Pa). 5.4 Function alarm output The DPC310 has an open collector alarm output (terminal 7+ 8-); depending on the op- erating mode the function ist different. When an alarm occurs, an exclamation mark (!) indicates the alarm state (2nd line / 16th character).
  • Page 15: Measuring Mode

    The alarm delay time can also be set in the menu. Alarm ON: Output voltage steadily greater than: 0.95 • maxU for set alarm delay time Alarm OFF: Output voltage steadily less than: 0.9 • maxU for set alarm delay time Alarm ON = low resitance, Alarm OFF = high resistance 5.4.2 Measuring mode: For limit value monitoring, a limit value can be entered under the menu item “limit switch”.
  • Page 16: Extern 0

    ΔP > 1,05 x limit value for set switching delay time 5.5 Extern 0...10 V dc input All DPC310 have an additional 0...10 V dc input (terminal 5+ 6-). On the one hand these input can be used for extern setpoint input e.g. for initialization or for application of dyna- mic setpoints in the installed state, without having to manually operate the device menu.
  • Page 17: Temperatur Controlled Setpoint

    All needed parameters are set in the DPC310, and the temperature ist displayed in the first display row. If the menu item ‚input function‘ is set to ‚temp ctrl setp‘, the next step is the input of temperature t1.
  • Page 18: Measuring Range Selection

    Set value in menu for ‘compensated setp’ 5.6 Measuring range selection The devices of the DPC310 series have each four adjustable measuring ranges, and are available in three measuring groups. Four preset measuring ranges in one device can be switched over in the menu.
  • Page 19: Maintenance

    OPERATION Maintenance The DPC310 contains no wearing or consumable parts. Servicing is not required. On request, Arthur Grillo GmbH offers an annual calibration with factory certificate. For information, please contact: Arthur Grillo GmbH Phone: +49 21 02 - 47 10 22...
  • Page 20: Specifications

    WARRANTY & SUPPORT 10. Specifications Measuring medium: Air or inert gases Measuring principle: Silicon diaphragm with spring and differential transformer Lowest span: 0...50 Pa Highest span: 0...6000 Pa Overpressure protection: 0.2 bar Static pressure: max. 0.2 bar Pressure connections: tubing 5 mm ø or 6 mm ø Enclosure: UL 94 HB;...
  • Page 21: Ce-Labelling

    SPECIFICATIONS 10.1 CE-labelling As an electric device the DPC310 falls within the scope of the directive 2004/108/EG (EMV-directive). In the scope of the EMV-directive the following norms were applied: DIN EN 61000-6-2:2006-03 Electromagnetic compatibility (EMC) - Part 6-2: Generic correction 1:2011-06...
  • Page 22: Ordering Information

    CE-LABELLING & ORDERING INFORMATION Ordering information Article Item no. Differential pressure controller DPC310-200: 2542 Measuring range 1: 0 ... 200 Pa or 0 ... 0,8 InH2O Measuring range 2: 0 ... 150 Pa or 0 ... 0,6 InH2O Measuring range 3: 0 ... 100 Pa or 0 ... 0,4 InH2O Measuring range 4: 0 ...

This manual is also suitable for:

Dpc310-1000 dpc310-200Dpc310-6000

Table of Contents