ONFIGURATION
MultiCOM 392 can be configured using the configuration software of the CSS.
Before setting the input/output, you must select "Multicom 392 [8out]" for I/O card model.
INPUT
IN1
REMOTE ON: By closing the contact for at least 3 seconds, the UPS will switch on.
IN2
REMOTE OFF: By closing the contact, the UPS will immediately switch off.
CONFIGURABLE INPUT: use the UPS configuration software to select the function that has to be
IN3
associated with IN3 (Input 3 mode default: Load on bypass).
Manual bypass auxiliary contact (for the management of an auxiliary contact of a possible remote
bypass). The auxiliary contact must be anticipated type, normally open.
SWMB
The inputs IN1 / IN2 / IN3 have to be used as alternative to the corresponding inputs on the AS400 port of the UPS.
The transition takes place regardless of the status of the bypass line and of the bypass/inverter
sync.