Riello MultiCOM 392 User Manual page 15

Table of Contents

Advertisement

For each of the eight outputs can be selected: the associated event (Output mode), the operating logic of the relay
(Logic) and a delay (in seconds) in reporting the event.
Output
OUT 1
OUT 2
OUT 3
OUT 4
OUT 5
OUT 6
OUT 7
OUT 8
EXAMPLE 1 - if you set an output in this way:
the relative contact will be:
UPS working by mains
EXAMPLE 2 - if you set an output in this way:
the relative contact will be:
UPS working by mains
- MST / MSM / MCT / MCM -
OUTPUT CONTACTS DEFAULT CONFIGURATION
Output mode
Battery low
Battery working
Inverter locked
Load on bypass
UPS OK
Battery fail
Overload
Any alarm
Output mode
Battery working
Output mode
Battery working
Logic
Normal OFF
Normal OFF
Normal OFF
Normal OFF
Normal OFF
Normal OFF
Normal OFF
Normal OFF
Logic
Normal OFF
UPS in battery working mode
Logic
Normal ON
UPS in battery working mode for at least 10 seconds
15
Delay (s)
0
0
0
0
0
0
0
0
Delay (s)
0
Delay (s)
10