Download Print this page

Task Force Tips INDUSTRIAL Series Instructions For Safe Operation And Maintenance

Deluge nozzles with fixed & selectable flow

Advertisement

Quick Links

INDUSTRIAL & MASTERSTREAM 1000
INSTRUCTIONS FOR SAFE OPERATION AND MAINTENANCE
WARNING
TASK FORCE TIPS, Inc.
Made in USA • www.tft.com
©Copyright Task Force Tips, Inc. 1998-2004
MANUAL: Deluge Nozzles
With Fixed & Selectable Flow
Read instruction manual before use. Operation of this device without understanding the
manual and receiving proper training is a misuse of this equipment. A person who has not
read and understood all operating and safety instructions is not qualified to operate the
Industrial and Masterstream nozzle.
This instruction manual is intended to familiarize firefighters and maintenance personnel
with the operation, servicing and safety procedures associated with the Industrial and
Masterstream firefighting nozzles.
This manual should be kept available to all operating and maintenance personnel.
1300, 2000, or 3000 LPM @ 7 BAR (700 KPA)
MASTERSTREAM 1000
500, 1000, 1500, 2000, 2500 LPM @ 7 BAR (700 KPA)
1000, 1500, 2000, 2500, 3000, 4000 LPM @ 7 BAR (700 KPA)
1200, 1800, 2400, 3000, 3600, 4800 LPM @ 10 BAR (1000 KPA)
MASTERSTREAM 1000
INDUSTRIAL
350, 500 or 750 GPM @ 100 PSI
SELECTABLE
250, 350, 500, 750, 1000 GPM @ 100 PSI
FIXED
1000 GPM MAX @ 100 PSI
4000 LPM MAX @ 7 BAR (700 KPA)
2800 E Evans Ave • Valparaiso , IN 46383-6940 USA
800-348-2686 • 219-462-6161 • Fax 219-464-7155
LIM-035 October 5, 2004 Rev02

Advertisement

loading

Summary of Contents for Task Force Tips INDUSTRIAL Series

  • Page 1 4000 LPM MAX @ 7 BAR (700 KPA) TASK FORCE TIPS, Inc. 2800 E Evans Ave • Valparaiso , IN 46383-6940 USA 800-348-2686 • 219-462-6161 • Fax 219-464-7155 Made in USA • www.tft.com ©Copyright Task Force Tips, Inc. 1998-2004 LIM-035 October 5, 2004 Rev02...
  • Page 2 2.0 GENERAL INFORMATION The Task Force Tips Industrial and Masterstream nozzles are deluge nozzles with clean far reaching straight stream. They are adjustable from straight stream to a dense fog pattern. Their rugged construction is compatible with the use of fresh water as well as fire fighting foam solutions.
  • Page 3 Stream Shaper / Bumper Halo Ring Baffle Coupling FIG 1A - Industrial Nozzle Stream Shaper / Bumper Halo Ring Coupling Flow Selector FIG 1B - Masterstream 1000 Selectable Gallonage Nozzle ©Copyright Task Force Tips, Inc. 1998-2004 LIM-035 October 5, 2004 Rev02...
  • Page 4 2.4.1 FOAMJET LX WITH MASTERSTREAM NOZZLE To increase the expansion ratio Task Force Tips "Foamjet LX" (model FJ-LX-M) may be used with the Masterstream nozzle. This low expansion foam tube attaches and detaches quickly from the nozzle. Note: As expansion ratio is increased, the reach of the stream will be decreased due to the greater amount of bubbles in the stream and their inability to penetrate the air.
  • Page 5 An indicator on the knob shows which flow has been selected. Figure 3 gives relationship of flow and pressure for various orifice sizes. FLOW (LPM) 1000 2000 3000 4000 900 1000 1100 1200 FLOW (GPM) FIG 3 - Nozzle Flow Characteristics ©Copyright Task Force Tips, Inc. 1998-2004 LIM-035 October 5, 2004 Rev02...
  • Page 6 F=.667 for metric units (LPM, MM, BAR) Note: 1 BAR=100 KPA is smooth bore nozzle flow in GPM (or LPM) nozzle is nozzle exit diameter in INCHES (or MM) is pitot pressure in PSI (or BAR) pitot ©Copyright Task Force Tips, Inc. 1998-2004 LIM-035 October 5, 2004 Rev02...
  • Page 7 3300 HORIZONTAL DISTANCE (METERS) CURVE FLOW REACTION INDUSTRIAL AND MASTERSTREAM 1000, 100 PSI (7 BAR, 700 KPA ) 1000 FLOW REACTION CURVE 1300 1900 2800 HORIZONTAL DISTANCE (FEET) 3800 ©Copyright Task Force Tips, Inc. 1998-2004 LIM-035 October 5, 2004 Rev02...
  • Page 8 6.0 WARRANTY Task Force Tips, Inc., 2800 East Evans Avenue, Valparaiso, Indiana 46383 ("TFT") warrants to the original purchaser of its Industrial and Masterstream series nozzles ("equipment"), and to anyone to whom it is transferred, that the equipment shall be free from defects in material and workmanship during the five (5) year period from the date of purchase.