Download Print this page

Task Force Tips INDUSTRIAL Series Instructions For Safe Operation And Maintenance page 2

Deluge nozzles with fixed & selectable flow

Advertisement

1.0
MEANING OF SAFETY SIGNAL WORDS
2.0
GENERAL INFORMATION
2.1
USE WITH SALT WATER
2.2
VARIOUS MODELS AND TERMS
2.3
PATTERN CONTROL
2.4
USE WITH FOAM
2.4.1
FOAMJET LX WITH MASTERSTREAM
NOZZLE
3.0
FLOW CHARACTERISTICS OF INDUSTRIAL
NOZZLE
1.0 MEANING OF SAFETY SIGNAL WORDS
A safety related message is identified by a safety alert symbol and a signal word to indicate the level of risk involved with a
particular hazard. Per ANSI standard Z535.4-1998 the definitions of the three signal words are as follows:
DANGER
WARNING
CAUTION
2.0 GENERAL INFORMATION
The Task Force Tips Industrial and Masterstream nozzles are deluge nozzles with clean far reaching straight stream. They are
adjustable from straight stream to a dense fog pattern. Their rugged construction is compatible with the use of fresh water as well as fire
fighting foam solutions. A summary of each nozzle's characteristics is shown in the tables below.
WARNING
SERIES
INDUSTRIAL
MASTERSTREAM
CUSTOMER SPECIFIED:
1000
FLOW
(GPM)
250, 350, 500, 750, 1000
NOTES ON TABLES:
!
2 ½ inch NH female threads are standard. Other threads and coupling sizes can be specified at time of order.
!
Industrial series nozzle is available in UNS C83600 brass or hardcoat anodized ANSI 356 aluminum.
!
Masterstream series nozzle is constructed of hardcoat anodized 6061-T6 aluminum.
!
Masterstream series nozzle is also available in automatic pressure control models. See catalog for details.
©Copyright Task Force Tips, Inc. 1998-2004
TABLE OF CONTENTS
DANGER indicates an imminently hazardous situation which, if not avoided, will result in death or
serious injury.
WARNING indicates a potentially hazardous situation which, if not avoided, could result in death or
serious injury.
CAUTION indicates a potentially hazardous situation which, if not avoided, may result in minor or
moderate injury.
This equipment is intended for use by trained personnel for firefighting. Their use for other
purposes may involve hazards not addressed by this manual. Seek appropriate guidance and
training to reduce risk of injury.
FIXED FLOW NOZZLES
FLOW
(GPM)
350, 500, 750
CUSTOMER SPECIFIED:
1000 GPM MAX
MASTERSTREAM SELECTABLE FLOW NOZZLES
PRESSURE
(PSI)
100
3.1
FLOW CHARACTERISTICS OF MASTERSTREAM
SELECTABLE NOZZLE
3.2
FLOW CHARACTERISTICS OF MASTERSTREAM
FIXED NOZZLE
3.3
DETERMINING FLOW WITH PRE-PIPED
MONITORS
3.4
STREAM TRAJECTORY DATA
4.0
FLUSHING DEBRIS
5.0
MAINTENANCE
6.0
WARRANTY
PRESSURE
(PSI)
1300, 2000, 3000
100
CUSTOMER SPECIFIED:
150 PSI MAX
4000 LPM MAX
FLOW
(LPM)
1000, 1500, 2000, 3000, 4000
1200, 1800, 2400, 3600, 4800
2
FLOW
PRESSURE
(LPM)
(BAR, KPA/100)
CUSTOMER SPECIFIED:
10 BAR MAX
PRESSURE
(BAR, KPA/100)
7
10
LIM-035 October 5, 2004 Rev02