Installation - ETC SC1008 Branch Circuit Emergency Lighting Transfer Switch Installation Manual

Table of Contents

Advertisement

ETC Installation Guide
SC1008 BCELTS
Fire Alarm Input
The Fire Alarm Input allows power transfer to the emergency power source (if emergency power is
present) when triggered by an external system.
Note:
The dry contact input can be configured for normally open or normally closed operation using switch
settings on the control board. Normally open and normally closed refer to the normal operational
state of the external circuit, not to the de-energized state of the external relay.
When the contact input is triggered, the unit will transfer to the emergency power source.
When the contact input trigger is removed, the unit will transfer back to the normal power
source, if present, or will remain on emergency power until normal power is restored.
Note:
connected between the input and the switch. Fire Alarm Inputs of up to ten SC1008 units
can be wired together using a single normally open or normally closed contact. See
Alarm Input on page 8
0–10 V Auxiliary Output
The 0–10 V Auxiliary Output provides an additional single pole relay that opens when the unit is in
the emergency state. This allows connection of 0–10 V or DALI ballasts that need the removal of the
control signal in order to illuminate at full in an emergency state.

Installation

Mounting and Conduit
1. Using the attached mounting plate, secure the SC1008 enclosure to a flat surface using four
1/4-20 mounting bolts or screws (provided by others).
Note:
orientation as needed for the installation. Simply remove the screws securing the mounting
plate to the SC1008 enclosure, rotate the plate 90°, reinstall the plate screws, and secure
the SC1008 unit to the installation location.
SC1008 rear view showing different mounting orientations
2. Temporarily remove the front cover to the unit.
SC1008 BCELTS
This transfer is activated even when normal power is still present.
The fire alarm input functions with up to 1,000 ft (300 m) of 18 AWG wire
for details.
The mounting plate on the SC1008 enclosure can be rotated 90° to change the
Page 3 of 11
Fire
ETC