Test Button; Laser Test; Fuse Replacement - ETC SC1008 Branch Circuit Emergency Lighting Transfer Switch Installation Manual

Table of Contents

Advertisement

ETC Installation Guide
SC1008 BCELTS

Test Button

Press and hold the "PUSH TO TEST" button to place the SC1008 into emergency mode and transfer
the load from normal power to emergency power. The SC1008 remains in emergency mode until
you release the "PUSH TO TEST" button. If emergency power is not present for the test, the SC1008
will remain in normal mode.

Laser Test

Directing a laser pointing device at the "LASER TEST" sensor located on the front of the SC1008
enclosure places the SC1008 into emergency mode and transfers the load from normal power to
emergency power. The SC1008 remains in emergency mode for 10 seconds and then returns to
normal mode. If emergency power is not present for the test, the SC1008 will remain in normal
mode.
Note:
ambient light environment such as outside in direct sunlight, a light blocking sticker is
included in the product packaging. Remove the adhesive backing and apply the sticker over
the laser test sensor to disable it.

Fuse Replacement

WARNING:
power to the panel before working inside could result in serious injury or death.
AVERTISSEMENT :
panneau sans avoir déconnecté le courant peut entrainer des blessures graves,
voire mortelles.
Before you begin pulling and terminating wire to the SC1008 BCELTS enclosure,
make sure the main circuit breaker cabinet or other readily accessible input
power disconnect device for both normal and emergency power input is locked
out and tagged out. Enclosures installed without an accessible input power
disconnect device cannot be serviced or operated safely. Follow all local codes
and restrictions. When the disconnect device is not located near the installed
enclosure, the disconnect must allow for proper lockout/tagout.
In–line fuses are present for the normal power input and the emergency power input. Replace fuses
only with Class G SLC 30 A fuses (order ETC part number F392).
1. Disconnect both power supply sources and lock/tag out appropriately.
2. Loosen the four screws and remove the cover.
3. Use a voltmeter to test if the fuses are functional, and replace the ones that have failed.
4. Replace the cover to the enclosure.
5. Reapply power from both sources and test the unit. See
instructions on testing the unit.
SC1008 BCELTS
If the laser test functionality is not desired, or the unit is to be installed in a high
RISK OF DEATH BY ELECTRIC SHOCK! Failure to disconnect all
RISQUE D'ELECTROCUTION! Travailler à l'intérieur du
Operation and Test on page 9