Address Assignment; Programming The As-I Address Of The Safety Output - bihl+Wiedemann BWU2236 User Manual

As-i safety relay output module with diagnostic slave 1 edm- and 2/1 safety inputs
Table of Contents

Advertisement

AS-i Safety Relay Output Module with Diagnostic Slave
1 EDM- and 2/1 safety inputs

Address Assignment

6.
Address Assignment
The device offers three different types of AS-i addresses:
Safety output
BWU2236 monitors communication on the safety address and switches based on the
monitored data.
ON
SEL
RUN
PRG
Information!
The address must be tested as described in Section Programming the AS-i address of
the safety output.
Safety input slave
One safety input slave which monitors the two contacts S1 and S2.
ON
SEL
RUN
PRG
Diagnostic slave
One standard-AS-i-Slave (AB-Slave) for diagnostics and switching under normal
operating conditions.
ON
SEL
RUN
PRG
6.1

Programming the AS-i address of the safety output

ON
SEL
RUN
PRG
Programming and monitoring of the address of the safety output is done
as described here:
ON
SEL
RUN
PRG
2.
Set desired address by using the hand-held addressing device or AS-i Mas-
ter.
3.
Check programmed address by using the hand-held addressing device or
AS-i Master.
4.
Check slave's ID code by using the hand-held addressing device or AS-i
Master. The code should be set to "F".
5.
Check slave's ID1 code by using the hand-held addressing device or AS-i
Master. Code should be the same as the tens-digit of the address.
Subject to technical modififications; no responsibility is accepted for the accuracy of this information
18
Internet: www.bihl-wiedemann.de • Flosswoerthstr. 41 • D-68199 Mannheim
This address can only be programmed if the switches are set to ON /
PRG.
This address can only be programmed if the switches are set to SEL /
PRG.
This address can only be programmed if the switches are set to SEL /
RUN.
Basic position
1.
Set the switches of the device to ON/PRG.
© Bihl+Wiedemann GmbH
phone: +49 621 33 996-0 • fax: +49 621 3 39 22 399

Hide quick links:

Advertisement

Table of Contents
loading