Starting Procedures
When using this product for the first time, pursue work while making sure to avoid omission and incorrect
wiring by referring to the procedure below. "PC" stated in this section means "PC software".
This section explains the procedure for starting up the Gateway Unit. For the settings and wiring of each of
the individual devices, controllers, and actuators connected to the network, refer to the individual device's
Instruction Manual.
Check of Packed Items
No→
Has everything been received?
Contact us or our distributor.
Yes
Point Check Item
Installation and Wiring
• Is frame ground (FG) connected?
Following Instruction Manual and this guide, set Gateway Unit
• Has the noise countermeasure been taken?
and have the wirings for the network and SIO completed.
• Is the terminal treatment conducted on the shielded wire?
Also, have all the wirings done for the power supply, actuator
• Is the terminal resistance connected?
motor and encoder cable following the instructions on the
Instruction Manual for each controller.
←Yes
Initial Settings of Gateway Unit
Ensure the settings for the mode, field network baud rate and
node addresses (station numbers) comply with the system.
Initial Settings of IAI Controller Connected to Gateway Unit
• Have the settings for axis numbers.
• Have the setting for Parameter No. 16 SIO Baud Rate to 230.4kbps.
• Have the setting for Parameter No. 17 Slave Station Transmitter Activation Minimum Waiting Time to 2msec.
• Have all other necessary parameter settings done.
PLC (Master Unit) Baud Rate
Important Check Item
Have the settings for the node addresses (station numbers)
Is the programmed Gateway control sequence
and baud rate.
complied with the operation mode and the system?
←Yes
Power Supply
1) Supply the power to the IAI controller that is connected to Gateway Unit.
2) Supply the power to Gateway Unit
3) Supply the power to PLC (master unit)
Communication Establishment Check
→No
Reconfirm all the settings following the procedure
• Confirm that the communication has been established by checking
in this chart while referring to the Instruction Manual
the monitor LEDs on Gateway Unit.
for each unit, controller and PLC.
[Refer to Troubleshooting Section.]
• Are the LEDs turned on in normal condition? Is PLC (master unit)
side also in normal condition?
(Note) Refer to the PLC and master unit instruction manuals for the
details how to check on the master unit side.
↓ Yes
Communication is established. Move on to the system operation check and adjustment.

Troubleshooting

On Gateway Unit, there are the monitor LEDs for the field network and SIO communication.
You can confirm the communication establishment and also communication errors on these LEDs.
1. DeviceNet (RCM-GW-DV)
Gateway Unit Status Display LEDs
LED
Color
Indication
Illuminating CPU is in process.
RUN
GN
The power is OFF or CPU is not working. Please contact us if
OFF
the LED does not turn ON even after the power is turned ON.
Illuminating CPU error. Please contact us.
G.ER
RD
OFF
CPU is operating in normal condition.
Either an error is occurred on DeviceNet module or the
connection with DeviceNet is not established.
Check the communication status LEDs for the connection to
Illuminating
DeviceNet, and check the settings and wirings. Even if this LED
is ON, the connection to the teaching tool is available as long as
C.ER
RD
RUN is turned ON.
The port switch is ON. The interval for the flashing should be
Flashing
1sec.
OFF
Status is in normal condition.
There is a communication
error occurred to all the
Illuminating
axes that are in SIO
communication with the
connected IAI controller.
There is a communication
T.ER
RD
error occurred to one or
more of the axes that are
Flashing
in SIO communication
with the connected IAI
controller.
OFF
Status is in normal condition.
DeviceNet status indicator LEDs (MS: Node condition, NS: Network condition)
LED
Color
Indication
Illuminating The machine is in the normal operation.
GN
Connection to the master is not established.
Flashing
Check if it has been registered in the master's scanning list.
A hardware error occurred.
Illuminating
MS
Board must be replaced. Please contact us.
RD
There is an error occurred but it is not critical such like a
Flashing
configuration error or incorrect switch settings.
It can be recovered with a rebuild of the settings.
Power is not supplied.
OFF
The connection has been established and the communication is
Illuminating
being performed normally.
GN
Online but network connection is not yet established.
Flashing
Communication Stop (Network is normal). Check the scan list.
A communication error has
occurred. The communication
cannot be established due to a
Illuminating
NS
duplication of node addresses or a
RD
Busoff (communication stop due to
frequent data error detection).
A communication error has
Flashing
occurred.
(Communication time-out is detected.)
The machine is not on-line. The power to the DeviceNet is not
OFF
supplied.
Refer to Instruction Manual for the details of the DeviceNet status check.
SIO Communication Status Display LEDs
LED
Color
Indication
Flashing
Data is being sent (from Gateway Unit to IAI controller).
TxD
GN
Data sending is being stopped (from Gateway Unit to IAI
OFF
controller).
Flashing
Data is being received (from IAI controller to Gateway Unit).
RxD
GN
Data receiving is being stopped (from IAI controller to Gateway
OFF
Unit).
2. CC-Link (RCM-GW-CC)
Description
• Check the settings in the
parameters (No. 16 and 17) for
each axis controller.
• Check the axis number settings.
• Check the wiring connections of
SIO communication lines.
• Check the terminal resistance
devices.
• Check the noise prevention
equipment.
Description
Check the node address
settings, baud rate
setting, communication
line wiring connections,
terminal resistance
connections,
communication power
supply, noise prevention,
etc.
Description
Gateway Unit Status Display LEDs
LED
Color
Indication
Description
RUN
Illuminating CPU is in process.
GN
The power is OFF or CPU is not working. Please contact us if
OFF
the LED does not turn ON even after the power is turned ON.
Illuminating CPU error. Please contact us.
G.ER
RD
OFF
CPU is operating in normal condition.
Either an error is occurred on CC-Link module or the connection
with CC-Link is not established.
Check the communication status LEDs for the connection to
Illuminating
CC-Link, and check the settings and wirings. Even if this LED is
ON, the connection to the teaching tool is available as long as
C.ER
RD
RUN is turned ON.
The port switch is ON. The interval for the flashing should be
Flashing
1sec.
OFF
Status is in normal condition.
T.ER
There is a communication
• Check the settings in the
error occurred to all the
parameters (No. 16 and 17) for
Illuminating
axes that are in SIO
each axis controller.
communication with the
• Check the axis number settings.
connected IAI controller.
• Check the wiring connections of
SIO communication lines.
There is a communication
RD
• Check the terminal resistance
error occurred to one or
devices.
more of the axes that are
Flashing
• Check the noise prevention
in SIO communication
equipment.
with the connected IAI
controller.
OFF
Status is in normal condition.
CC-Link status indicator LEDs (MS: Node condition, NS: Network condition)
LED
Color
Indication
Description
The machine is in the normal operation. (Illuminated once
Illuminating
communication started)
RUN
GN
Not in the network or timeout (The illumination is turned off if the
OFF
communication is shut off for a certain time.)
Illuminating Baud rate or station number setting is not correct.
Error in reception data to self station. (CRC error : Data error is
ERR
RD
Flashing
detected)
OFF
Status is in normal condition.
Illuminating Data is being received.
RD
GN
OFF
There is no received data.
Flashing
Data is being sent.
SD
GN
OFF
There is no sent data.
Refer to Instruction Manual for the details of the CC-Link status check.
SIO Communication Status Display LEDs
LED
Color
Indication
Description
Flashing
Data is being sent (from Gateway Unit to IAI controller).
TxD
GN
Data sending is being stopped (from Gateway Unit to IAI
OFF
controller).
Flashing
Data is being received (from IAI controller to Gateway Unit).
RxD
GN
Data receiving is being stopped (from IAI controller to Gateway
OFF
Unit).