Siemens SION 3AE5 Operating Instructions Manual page 39

Vacuum circuit-breaker
Table of Contents

Advertisement

Fig. 52
Example - Mounting the retaining angle for the
cable outlet
9229 0025 176 0A
2019-08-05
Mounting the retaining angle for the cable outlet
The version with plug or terminal strip (without low-voltage plug) is supplied with a
retaining angle (60) and fixing materials in the supplementary equipment. The re-
taining angle serves to bundle and protect the cables coming from the low-voltage
interface.
Self-tapping screws are suitable for single use only.
3 ±0.3 Nm
Mount the retaining angle (60) with the cable harness so
that the cable harness is routed to the back of the pole
shells.
Fit the retaining angle with the self-tapping screws (Torx
screwdriver, size 20) and a tightening torque of
3 ±0.3 Nm.
For the wiring of the connector strip or terminal strip refer
to page 46.
Installation
39