5 Installation

The work described in this section is only to
be performed by personnel appropriately
qualified to carry out such tasks.

5.1 Installation conditions

Work position
The work position for the regulator is the
front view onto all operating controls on the
regulator (including any additional fittings)
seen from the position of operating person-
nel.
Plant operators must ensure that, after instal-
lation of the device, the operating personnel
can perform all necessary work safely and
easily access the device from the work posi-
tion.
Pipeline routing
The inlet and outlet lengths vary depending
on several variables and process conditions
and are intended as recommendations. Con-
tact SAMSON if the lengths are significantly
shorter than the recommended lengths.
To ensure that the regulator functions proper-
ly, proceed as follows:
Î Observe the inlet and outlet lengths (see
Table 5-1). Contact SAMSON if the reg-
ulator conditions or state of the medium
process deviate.
Î Install the regulator free of stress and
with the least amount of vibrations as
possible. Read information under
'Mounting position' and 'Support or sus-
pension' in this section.
EB 3009 EN
Î Install the regulator allowing sufficient
space to remove the actuator and valve
or to perform service work on them.
Mounting position
To ensure that the regulator functions
properly, proceed as follows:
Î DN 15 to 150/NPS ½ to 6: Install the
actuator housing suspended downward
in horizontal pipelines (see sec-
tion Fig. 5-1).
Î DN 200 and 250/NPS 8 to 10: Install
the actuator housing upright on top in
horizontal pipelines (see sec-
tion Fig. 5-1).
Î Make sure the direction of flow matches
the direction indicated by the arrow on
the body.
Î Contact SAMSON if the mounting posi-
tion is not as specified above.
NOTICE
!
Possible malfunction and damage due to
adverse weather conditions (temperature,
humidity).
− Do not install the regulator outdoors or in
rooms prone to frost.
− Protect the regulator against frost if it is
used to control freezing media.
− Either heat the regulator or remove it from
the plant and completely drain the residual
medium.
Installation
5-1