S&P ECOAIR LC Series Manual page 18

Centrifugal extractor fans
Hide thumbs Also See for ECOAIR LC Series:
Table of Contents

Advertisement

Available languages
  • EN

Available languages

  • ENGLISH, page 16
EcoAIR SLC
1. Continuous operation only on tric-
kle setting (Fig. 3).
Once the air volume set the fan is
connected to the mains and the
unit will operate continuously at
this air volume.
2. Continuous operation on trickle
with ability to boost at high speed.
The EcoAIR SLC is connected to
an external switch or light switch.
When the switch is closed, the fan
runs at full speed until the switch
opens again (light off):
Fig.4a - Wiring diagram to boost
the fan with the light switch.
Fig.4b - Wiring diagram to boost
the fan with a separate switch.
3. Intermittent operation: The extrac-
tor runs at the pre-set speed when
the switch is closed:
Fig.4a - Wiring diagram to switch
on the fan with the light switch.
Fig.4b - Wiring diagram to switch
on the fan with a separate switch.
Start-up timer function:
In this operation, the "start-up ti-
mer function" allows to delay the
extractor start-up for a period of 50
seconds. So that, for example, the
fan does not switch on if the usage
time of the bathroom is less than
50s.
If you exceed the 50s, the fan swit-
ches on, and when the light swit-
ches off, runs the time set by the
timer.
This function is selected
with the dip-switch 8.
18
EcoAIR TLC
This model is provided with an adjus-
table over-run timer.
The selection of the run on time is
done with the dip-switches 6 and 7:
setting between 1, 5, 15 and 30 mi-
nutes.
Factory setting: 1 minute
1. Continuous operation: The timer
allows the fan to continue to ope-
rate in high speed for the selected
period after the switch has been
turned off.
Fig.4a - Wiring diagram to boost
the fan with the light switch.
Fig.4b - Wiring diagram to boost
the fan with a separate switch.
2. Intermittent operation: The timer
allows the fan to continue to opera-
te for the selected period after the
switch has been turned off (fi g.4a
and 4b).
Start-up timer function:
In this operation, the "start-up timer
function" allows to delay the extrac-
tor start-up for a period of 50 se-
conds. So that, for example, the fan
does not switch on if the usage time
of the bathroom is less than 50s.
If you exceed the 50s, the fan swit-
ches on, and when the light switches
off, runs the time set by the timer.
This function is selected
with the dip-switch 8.

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ecoair lc ecowatt seriesEcoair lc

Table of Contents