INSTRUCTION
EN
TTC63F
i
Read this instruction before installation
and wiring of the product
Consult documentation in all cases where this symbol
is used, in order to find out the nature of the potential
hazards and any actions to be taken
Thyristor controller for proportional control of
electric heating
TTC63F is a proportional, 3-phase electric heating controller with
automatic voltage adjustment. The controller operates through step-
less, time-proportional control, where the relationship between the
on-time and off-time is based on the current heat demand.
The controller is primarily intended for use together with Regin's
NTC series of sensors for either supply temperature control or room
temperature control. During room temperature control, the supply air
temperature can be provided with a minimum or maximum limitation.
TTC63F can control both symmetrical Y-connected 3-phase heaters
and symmetrical or asymmetrical Delta-connected heaters.
The controller is only intended for control of electric heating. The
control principle makes it unsuitable for control of motors or lighting.
TTC63F is intended for DIN-rail mounting.
Technical data
Supply voltage
3-phase, 400 V AC +/- 10 % 3-phase,
50...60 Hz with automatic voltage adaptation.
Max. current: 63 A/phase.
Max. load
14500 W/phase at 400 V line voltage (63 A)
Min. load
1100 W/phase at 400 V line voltage (5 A)
Protection class
IP20
Ambient temp.
0...40°C, non-condensing
Installation
Mount TTC63F on a DIN-rail in a cabinet or other casing.
Mount the controller vertically with the text right side up.
NOTE: At full power, TTC63F will emit approx. 120 W
of excess heat which must be properly dissipated!
Wiring
Connect the supply voltage to the terminals L1in, L2in and L3in.
1
2 3 4 5 6 7 8 9
L1 L2 L3 L3 L2 L1
1 1
3
Figure 1: Wiring of supply voltage and load
NOTE: The controller must be grounded and the supply
voltage must be interlocked via a high temperature limit switch!
Load
Use terminals L1out, L2out and L3out.
Resistive 3-phase heater without neutral connection.
Main sensor and external setpoint (figures 2-6)
Use terminals 1 and 4 (polarity insensitive). Low voltage.
NOTE: Terminals 2 and 3 are internally connected and are
used to simplify wiring when using an external setpoint
potentiometer. Switch 1 is used to select internal or external
setpoint.
TTC63F
TG-R5xx
1 2
3 4
TG-R6xx
1
2
Figure 2: Wiring of room temperature sensor TG-R5xx
or TG-R6xx when using internal setpoint
1 2
3 4
TG-R4xx
1
3
Figure 3: Wiring of TG-R430 sensor as external sensor and
setpoint adjustment for room control
1 2
3 4
TG-K3xx
TG-G1xx
Figure 4: Wiring of floor or duct sensor when using
internal setpoint
TG-K3xx
1 2
3 4
TG-R4xx
TG-G1xx
2
3
Figure 5: Wiring of an external, separate sensor and TG-R4xx as a
setpoint device only
TG-K3xx
1 2
3 4
TBI-xx
TG-G1xx
1
2
Figure 6: Wiring of an external, separate sensor and a TBI-xx
potentiometer as a setpoint device
1

Advertisement

loading

Summary of Contents for Regin TTC63F

  • Page 1 TG-R6xx when using internal setpoint Ambient temp. 0...40°C, non-condensing Installation Mount TTC63F on a DIN-rail in a cabinet or other casing. Mount the controller vertically with the text right side up. TG-R4xx NOTE: At full power, TTC63F will emit approx. 120 W...
  • Page 2: Control Principle

    NOTE: TG-K360 must be used. 0°C and 10 kΩ at 30°C. The resistance changes by 167 Ω/°C. TTC63F can also be used for control with an external 0...10 V DC control signal from another controller. Leave the sensor terminals disconnected. Set all switches to...
  • Page 3: Installation

    Montera TTC63F på DIN-skena i apparatskåp eller annan kapsling. Montera regulatorn lodrätt med texten rättvänd. TG-R4xx OBS: TTC63F avger vid full effekt cirka 120 W förlustvärme som måste kylas bort! Inkoppling Figur 3: Inkoppling vid rumsreglering med TG-R430 som extern Anslut matningsspänningen till plintarna L1in, L2in och L3in.
  • Page 4 Extern styrsignal för sig. Potentiometerns resistans varierar 0...5 kΩ mellan min- Önskade begränsningstemperaturer ställs in med potentiometrarna TTC63F kan också användas för styrning med extern 0...10 V DC styrsig- och maxläget. Givarens resistans varierar 15 kΩ...10 kΩ mellan Min och Max.
  • Page 5 2 3 4 5 6 7 8 9 L1 L2 L3 L3 L2 L1 Der Regler ist ausgelegt die Regin NTC Fühlerserie für die Zuluft- oder Raumluftregelung zu nutzen. Während der Raumtemperaturregelung kann die Zulufttemperatur minimal oder maximal begrenzt werden.
  • Page 6 Proportionalbereich von 1.5 K. Externes Stellsignal TG-R4xx TG-K360 TTC63F kann auch mit einem 0...10 V DC Stellsignal eines anderen Reglers arbeiten. Abb. 7: Anschluss des Begrenzungsfühlers Entfernen Sie die Drahtbrücke zwischen Klemme 7 und 9 und schliessen Sie das Stellsignal wie in Abb. 8 gezeigt, an.
  • Page 7 TG-K330 hat 15 kΩ bei 0°C und 10 kΩ bei 30°C. Der Wider- des europäischen Parlamentes und des Rates durch EN 50581:2012. stand verändert sich um 167 Ω/°C. Le TTC63F est un régulateur de puissance triphasé progressif pour Kontaktadresse la commande de chauffage électrique offrant une adaptation automa- Schliessen Sie die Fühler noch nicht wieder am Regler an.
  • Page 8 Installation Sonde de limite Bornes 5 et 6. Indépendantes de la polarité. Basse tension. Monter le TTC63F sur un rail DIN dans une armoire ou un autre TG-R5xx En cas de régulation de la température ambiante, les valeurs max et coffret.
  • Page 9 RoHS varie entre 0 - 5kΩ entre les positions min et max. La résistance TTC63F peut aussi fonctionner avec un signal 0...10 V DC émis par Ce produit répond aux exigences de la directive 2011/65/UE du de la sonde varie entre 10kΩ et 15kΩ entre les températures min un autre régulateur.