Operation; Ventilation; Warning - Lavor FF45 User's Manual & Operating Instructions

Table of Contents

Advertisement

Fueling The Heater:
Paraffin
For optimal performance of this heater, it is
strongly suggested that paraffin be used.
paraffin has been refined to virtually eliminate
contaminants, such as sulfur, which can cause
a rotten egg odor during the operation of the
heater. Using diesel fuel can cause excess soot
production. Do not use Bio-Diesel as this fuel will
damage your heater's seals and filter.
NEVER REFUEL THIS HEATER
DANGER
WHILE IT IS HOT OR
OPERATING. FIRE OR EXPLOSION COULD
RESULT.
NEVER FILL THE FUEL TANK
CAUTION
INDOORS. ALWAYS FILL
THE TANK OUTDOORS. BE SURE THAT
THE HEATER IS ON LEVEL GROUND WHEN
FUELING, AND NEVER OVERFILL THE TANK.
DO NOT USE GASOLINE OR

WARNING

CRANKCASE DRAININGS.
- NEVER use fuel such as benzene, alcohol, white
gas, camp stove fuel, paint thinners, or other oil
compounds in this heater. THESE ARE VOLATILE
FUELS THAT CAN CAUSE A FIRE OR
EXPLOSION.
- NEVER store kerosene in the living space.
Kerosene should be stored in a well ventilated area
outside the living area.
- NEVER store kerosene in direct sunlight or near a
source of heat.
- NEVER use kerosene that has been stored from
one season to the next. Kerosene deteriorates
over time. OLD Kerosene WILL NOT BURN
PROPERLY IN THIS HEATER.
NOTE: Kerosene should only be stored in a blue
container that is clearly marked "Kerosene."
Never store kerosene in a red container. Red is
associated with gasoline.
© 2020, Lavorwash
NEVER LEAVE HEATER UNATTENDED WHILE BURNING OR
WHILE CONNECTED TO A POWER SOURCE

Operation

7

Ventilation:

- Risk of indoor air pollution and Carbon
Monoxide Poisoning. Use heater only in well
ventilated areas.
- Refer to Safety Information on pages 1-2 for
information about Carbon Monoxide Poisoning.
- ALWAYS provide a fresh air opening in the heated
space of at least 2,800 cm
heater output. Provide a larger opening if more
heaters are being used.
CARBON MONOXIDE POISONING
DANGER
MAY LEAD TO DEATH!
Minimum Ventilation Opening Needed
FF45
FF70
1.4 ft.²
2.1 ft.²
1300 cm²
1951 cm²
This appliance is designed to
WARNING
operate safely at a minimum
ambient temperature of -20° C.
Use caution when servicing in
WARNING
wet areas. Disconnect power
from the power mains and keep all electrical
components from becoming wet. Only a
qualified technician should service the
heater
A qualified technician is
WARNING
required to install, adjust and,
where necessary, convert this heater for use
with other fuel types.
Kerosene Forced Air Heater User's Manual
for each 29 kW of
2
FF125
FF175
3.8 ft.²
5.3 ft.²
3530 cm²
4924 cm²
FF215
6.5 ft.²
6039 cm²

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ff70Ff125Ff175Ff215