OPERATING AND SAFETY CONTROL SET POINT GUIDE
Below you will nd all our standard electrical controls listed with
the recommended settings at di erent operating conditions.
ese settings are based on systems using Refrigerant R404A
CONTROL
High Pressure Control
Low Pressure Control
Freeze Control ( PENN P29NC-3)
High Pressure Control
Low Pressure Control
Freeze Control ( PENN P29NC-3)
High Pressure Safety
Low Pressure Control
Freeze Control ( PENN P29NC-3)
High Pressure Safety
Low Pressure Control
Freeze Control ( PENN P29NC-3)
Please check the set point before starting the system.
Unauthorized adjustment of freeze protection will void the warranty. Please consult the
factory ( 253-735-9466 ) prior to adjusting the setpoint.
On remote or air remote condensing unit systems, operating controls may have to be defeated to allow for system
charging of refrigerant. Be sure to set reset any defeated controls before completing start-up procedures.
To order a refractometer (glycol solution tester) please contact your sales
representative or contact the factory at the above listed phone number
DESIRED
GLYCOL
CUT IN
CUT OUT
TEMP
400 psi
25 °F
30 psi
10 psi
25 °F
30 psi
25 °F
400 psi
30 °F
30 psi
10 psi
30 °F
35 psi
30 °F
400 psi
35 °F
30 psi
10 psi
35 °F
35 psi
35 °F
400 psi
40 °F
30 psi
10 psi
40 °F
40 psi
40 °F
Packaged Glycol Chiller Systems | 17
GLYCOL
FREEZE
POINT
GLYCOL %
0 to -10°F
36-42%
0 to -10°F
36-42%
0 to -10°F
36-42%
0 to 5°F
33-36%
0 to 5°F
33-36%
0 to 5°F
33-36%
0 to 5°F
33-36%
0 to 5°F
33-36%
0 to 5°F
33-36%
0 to 10°F
30-36%
0 to 10°F
30-36%
0 to 10°F
30-36%