16 | Pro Refrigeration, Inc
CHILLER MODEL #:
CHILLER SERIAL #:
CUSTOMER :
START-UP DATE :
PRE START-UP CHECK LIST
All Electrical Connections are tight, these may loosen during shipment
Main Disconnect Energized for 24Hr. to allow Crankcase Heater to boil any liquid refrigerant out of crankcase.
Field Process Piping has been leak checked
VOLTAGE on Chiller System matches customer supplied VOLTAGE
Glycol / Water Solution freeze point is at least 20 F. (11 C.) below T-Stat Setpoint
Glycol Pump Motors Rotation is CLOCKWISE when viewed from motor end
Glycol Storage Tank is at least 80% Full
Pressure Bypass Valve tested. To test, Close a valve on the Glycol Supply and visually check for return flow into storage tank.
Chiller location allows adequate air flow to and from Air Cooled Condenser. (Air Cooled Only)
Adequate water supply provided to Water Cooled Condenser (Water Cooled Only)
X
Percentage of Propylene Glycol to Water in System
Glycol / Water Solution freeze point (Refractor Reading)*
Incoming Line Voltage Reading (L1-L2, L2-L3, L1-L3)
Control Transformer Secondary Voltage Reading
Circulation Pump Motor Amp Readings
Process Pump Motor Amp Readings
PRESSURE CONTROL SETTINGS (refer to Operation Manual for Factory Settings)
High Pressure Cut-Out
Low Pressure Cut-In
Low Pressure Cut-Out
Oil Failure Control
P29NC-3 FREEZE PROTECTION SETTINGS (refer to Operation Manual for Factory Settings)
Low Pressure Cut-Out
TEMPERATURE CONTROL SETTINGS (refer to Operation Manual for Factory Settings)
Setpoint Temperature
Differential Setting
OPERATING DATA**
Glycol Solution Temperature (Thermostat Display Temp.)
Suction Pressure (PSI)
Suction Line Temperature at Compressor
Discharge Line Pressure (PSI)
Discharge Line Temperature
Liquid Line Pressure (PSI)
Liquid Line Temperature
Glycol Temperature at Evaporator Inlet
Glycol Temperature at Evaporator Outlet
Ambient Air Temperature
Condenser Water Temperature Inlet & Outlet (If applicable)
Compressor Amp Draw
Complete Chiller System Amp Draw
* A Refractometer should be used to obtain the actual Glycol Solution Freeze Point. To order a Refractometer please
call Technical Assistance at (253) 735-9466, these are also available from most propylene glycol suppliers.
** Operating Data should be recorded in the order listed. To determine proper operation of the chiller system, please
record all Data simultaneously, or record all data completely with-in as short of period as possible. Data should
be recorded at different Glycol Operating Temperatures (example: record at 45 F. / 35 F. / 25 F.)
FOR TECHNICAL ASSISTANCE CALL (253) 735-9466 , Monday thru Friday 6:00 AM TO 5:00 PM PACIFIC STAND. TIME
TECHNICIAN:
SIGNATURE:
CHILLER SYSTEM START-UP SHEET
DESCRIPTION
7-2
DATA #1
DATA #2
DATA #3
COMPANY:
TEL. #:
DATA #4