Push Button

Local Mode
OPEN
Open Command
Local Mode
STOP
Stop Command
Local Mode
CLOSE
Close Command
Actuator Setting
Place the selector switch in "OFF" position and press the
open and close button for over 2 seconds to enter the
setting mode
OPEN
OPEN
Setting Menu Up:
Setting Menu Up:
Setting Menu Down:
Setting Menu Down:
CLOSE
Setting Reset:
Setting Reset:
STOP
Setting Enter:
Setting Enter:
STOP
Set Up Menu
INCH / HOLD
Two operating modes of Inching / Hold
Inching Push to run
Holding Mantained
Decision of behavior for
ESD DIR
Emergency shut down signal
Close
Actuator move to full close position
Open
Actuator move to full open position
Stop
Actuator position: Stop
Off Mode
Manu Up Scroll
Off Mode
2 ~ 3 sec: Enter
1 sec: Escape
Off Mode
Menu Down Scroll
● Open & Close Press ●
CLOSE
( 1 sec )
( 1 sec )
( 1 sec )
( 1 sec )
( 1 sec )
( 1 sec )
( 2~3 sec )
( 2~3 sec )
www.rotork.com www.remotecontrol.se
Decision of the seating method in
TQ CHECK
Limit Position
TQ Check On Open, Close, Over Torque
TQ Check Off Full Open / Close Limit
You can choose seating method, Limit or Torque.
The Original set condition would be "Limit"
seating when shipped.
CYCLE
Check of the total cycle
You can check the total cycle which was
operated so far.
Total memory capacity is 100,000 cycle.
1 cycle: Full close & Full Open
Check of Potentiometer (0 ~ 1000kΩ)
PIU CHECK
0 ~ 120Ω : Actuator Full Close
AUTO SCAN
Actuator auto calibration
Start Ascn
Auto Scan "Start"
Stop Ascn
Auto Scan "Stop"
DEAD BAND
Adjustment of Dead Band valve.
Dead Band in an area of a signal range or band
where no action occure.
The valve is adjustement between 1% and 5% in
0,5% increment.
The original set value is 2% when shipped.
TIME DELAY
Adjustment of Time Delay valve.
Time Delay means that implementation of any
signal is delayed when any input signal is above
dead band.
The valve is adjustment between 0,5sec and
5sec in 0,5sec increment.
The original set value is 1,0sec when shipped.
Decision of behavior for input fault signal.
FAULT DIR
Fail Dir Close Actuator "Full Close"
Fail Dir Open Actuator "Full Open"
Fail Dir Stop Actuator "Stop"
ESD DIR
Program Reset
- 6 -