Functions - WEG CPW22 User Manual

Emergency stop control
Table of Contents

Advertisement

Available languages

Available languages

General Information
NOTE!
Depending on the application and configuration some features can be not reached.

2.2 FUNCTIONS

The CPW22 is powered (A1 / A2) with extra-low voltage (SELV / PELV). The internal logical system closes the safety
contacts when the monitored safety inputs is closed and start button (S21) is pressed.
When the monitored safety inputs is opened (S12 / S13 / S14), the output contacts (13-14 / 23-24 / 33-34), forced
guided, are opened and safely shutdown the machine. It is ensured that a single fault does not lead to the loss
of the safety function and that every fault is detected by self-monitoring in a cyclical manner, ensuring detection
after re-energization.
S21
START
POWER
+
A1
A2
SINGLE-CHANNEL SAFETY CIRCUIT
A single positively driven contact in the safety component is connected to the relay. This type of connection is
suitable for categories 1 or 2 according EN ISO 13849-1.
DUAL-CHANNEL SAFETY CIRCUIT
Two contacts of which at least one is a positively driven contact are connected to the relay. This type of connection
is suitable for categories 3 or 4 according EN ISO 13849-1.
RELAY START CONTROL
After the relay has switched off, the relay must be re-started, with manual or automatic start:
Manual start: The relay is started by actuating a button. Before the safety inputs must be re-established.
Automatic start: The relay switches on automatically as soon as the safety inputs changes back to the safe
state.
ATTENTION!
The renewed starting of the machine can only occurs automatically if it is ensured that there can be
no dangerous state.
6 | CPW22
S10
S11
S12
S13
+
LOGIC
-
-
Figure 2.1: Block diagram
S14
13
23
33
K1
K2
14
24
34
41
42

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents