Features

During normal standby, Output port (O1, O2) is
provided with Class B pathway supervision
when connects with 47KΩ EOLR (Part Number
30108524).
 Occupying one address. It can be modified in
filed.
 Output port utilizes AD sampling technology for
precise testing.
 Guide rail for installation, easy for construction.
 Compatible with GST-M200 and GST-IFP4M Fire
Alarm Control Panels (FACP).
 Standard: UL864, NFPA [70, 72].

Description

With a microprocessor, DI-M9305 Digital Single
Riser Output Module can communicate with a FACP.
The module is designed to switch on/off 24VDC
power at its output.

Connection and Cabling

Fig. 1 shows terminals on the module.
Fig. 1
(Z1, Z2) IN & OUT: Connecting with loop of FACP,
polarity-insensitive.
(I1, I2) IN & OUT: Power input terminals. For
connecting with 24VDC power from Listed FACP or
power supply.
O1, O2: Output terminals to 24VDC powered devices
CODE: connecting with P-9910B programmer.
Recommended Wiring
17 AWG or above fire cable for all terminals, and
subject to local codes.
30310200
DI-M9305
Digital Single Riser Output Module

Installation

Warning:
Before installing the module, disconnect
power from the loop and verify that the
guide rail is securely installed.
1)
Before installation, make sure the enclosure is
in good condition and markings are complete.
2)
The module shall either be installed in a North
America
standard
Minimum size is 4 in. square, 2-1/8 in depth (in
this case, standard box cover is required), or in
a UL Signaling Listed enclosure that provides
minimum wiring entries and spacing as shown
on Fig 2 and Fig 3. Minimum mounting space is
67×40.5mm.
3)
The module can be mounted on a guide rail as
shown on Fig 4.
4)
The module can also be installed in the
enclosure by 4 mounting screws as shown in
Fig.5.
metal
electrical
box.
Fig. 2
Issue 1.06
Fire Alarm
Equipment
47AU

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the DI-M9305 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for GST DI-M9305

  • Page 1  Occupying one address. It can be modified in filed.  Output port utilizes AD sampling technology for precise testing.  Guide rail for installation, easy for construction.  Compatible with GST-M200 and GST-IFP4M Fire Alarm Control Panels (FACP).  Standard: UL864, NFPA [70, 72]. Installation Description...
  • Page 2 Parameters used for O1/O2 setting includes: No checking Any other numbers(Default) Checking The system connection is shown in Fig. 6. Fig. 3 Z1 Z2 DI-M9305 Module Controlled Device 1 24VDC power line to next device Controlled Device N Fig. 4 47kΩ/1W End-of-line Resistor Fig.
  • Page 3 (with base) Weight About 66.6g (with base) This Data Sheet is subject to change without notice. Please contact GST for more information or questions. Gulf Security Technology Co., Ltd. No. 80, Changjiang East Road, QETDZ, Qinhuangdao, Hebei, P. R. China 066004 Tel: +86 (0) 335 8502434 Fax: +86 (0) 335 8502532 service.gst@fs.utc.com www.gst.com.cn...

Table of Contents