GST I-9301 Manual

GST I-9301 Manual

Addressable single i/o module

Advertisement

Quick Links

The Intelligent Solution

Features

 Two-wire
and
four-wire
programmed through hand held programmer.
 Electronic address can be modified in field.
 Built-in MCU processes messages intelligently.
 Monitoring power supply.
 Fault and action indicators available.
 Four wire output cable checking.
 Plug-in structure.
 Standard: EN 54-18:2005.

Description

I-9301 Addressable Single I/O Module works in
two-wire mode and four-wire mode.
In four-wire mode, on receiving start command from
the fire alarm control panel (FACP), it will close the
output relay to output 24VDC and illuminate the
Active indicator. If there is short, open circuit, or
power down, the module can check failure and report
it to the FACP.
In two-wire mode, on receiving start command from
the fire alarm control panel (FACP), it will close the
output relay to output normally-open normally close
contact signal and illuminate the Active indicator.

Connection and Cabling

Fig. 1 shows terminals on the module.
65
S+
S-
7
8
R
10
9
D1
D2
I-9301
Bottom Cover(Remove Top Cover And Terminal Plate)
Fig. 1
Z1, Z2: Connecting with loop of FACP , polarity-insensitive.
D1, D2: 24VDC power cable, polarity-insensitive
(only for four-wire mode).
S+, S-: Output for four-wire mode, polarity-sensitive.
Connecting with D1 (9), D2 (7) of C-9403. S+
connects with D1(9), and S- with D2(7).
NC, COM, NO: Normally open and normally close
terminals for two-wire mode.

Recommended Wiring

2
1.5mm
or above fire cable for 24VDC, 1.0mm
above fire cable for others, subject to local codes.
30308778
modes
can
be
Back Box
Conduit
Module
NO
COM NC
1
2
16
15
Z1
Z2
2
or
I-9301
Addressable Single I/O Module

Installation

The module is simply plugged onto the base after
corresponding terminals are connected.
If the cable conduit is on the surface of the wall, the
B-9310 Back Box is available. Note the upward
arrow for mounting direction (Fig.1).
Conduit
Fig. 2

Application

The module connects with fire control devices such
as lifts and fire doors which are activated by FACP.
The address and working mode of the module can
be programmable by a GST programmer in field.
Please refer to P-9910B Hand Held Programmer
Installation and Operation Manual for details. Factory
default mode is four-wire (number "1"). Two-wire
mode (number "2") can be programmed in field.
The module connects with C-9403 conventional
sounder strobe. Its system connection is shown in
Fig. 3. Working mode should be set to four-wire (1),
volt output for S+, S- should connect with 4.7kΩ
resistor in parallel (refer to Fig. 3).
B-9310
Back Box
Module
Issue 1.02

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the I-9301 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for GST I-9301

  • Page 1  Four wire output cable checking.  Plug-in structure.  Standard: EN 54-18:2005. Description I-9301 Addressable Single I/O Module works in two-wire mode and four-wire mode. In four-wire mode, on receiving start command from Installation the fire alarm control panel (FACP), it will close the...
  • Page 2 This document is subject to change without notice. Please contact GST for more information or questions. GST China GST UK GST Dubai Gulf Security Technology Co., Ltd.

Table of Contents