Addressable single i/o module

Advertisement

Quick Links

The Intelligent Solution

Features

Electronically addressed. The address can be
modified in field.
Built-in
microprocessor
intelligently.
Insulation technology for input signal, good
anti-interference ability.
Cable checking.
Plug-in structure.

Description

With a microprocessor, I-9301 Addressable Single I/O
Module can communicate with fire alarm control panel
(FACP), check power cut, control output and LED.
The module closes the output relay and illuminates the
LED when receiving start command from fire alarm
control panel.

Connection and Wiring

Terminals on the module are shown as Fig. 1.

Mounting

Hole
V+
G
COM1
NO1 NC1
7
8
9
10
D1 D2
Fig. 1
Z1,Z2:Connecting
with
polarity-insensitive.
D1, D2: Polarity-insensitive 24VDC power line.
V+,G:24VDC output terminals, supplying output contact
with +24V output signal . There is 24V output at V+ and
G no matter whether the module is started or not.
NC1, COM1, NO1: Normally closed or normally open
output terminals.
Recommended Wiring
2
1.5mm
or above fire cable for 24VDC power line,
2
1.0mm
or above fire cable for other terminals, subject
to local codes.

Installation

The module is simply plugged onto the base after
corresponding terminals are connected.
30303029
processes
messages
Mounting
GST-LD-8301/I-9301
Hole
Mounting
1
2
Direction
15 16
Z1 Z2
loop
of
FACP,
I-9301
Addressable Single I/O Module
Electric Box
Conduit
Module
Fig. 2
If the cable conduit is inside the wall, the base is
installed onto the electric box (Fig. 2). If the cable
conduit is on the surface of the wall, the B-9310 Back
Box is available.
Note the upward arrow for mounting direction (Fig.1).

Application

The module is designed to connect with the devices
controlled by fire alarm control panel, including smoke
exhauster, fan blower, and fire valve.
Address can be set through P-9910B programmer in
field, refer to P-9910B Hand Held Programmer
Installation
and
Operation
operation.
Mode of checking feedback signal can be set through
P-9910B programmer. After unlocking the programmer,
press Function and then number "4", input "13" or "40".
"13" means checking the feedback signal at any time,
"40" means checking feedback signal only in started
state. Press Program, if P appears on the screen, the
setting is successful.
The module can directly drive a smoke exhauster
or fire valve (electrical tripping device). System
composition is shown in Fig. 4.
548h/02
B-9310
Back Box
Conduit
Module
Fig. 3
Manual
for
specific
Issue 4.03

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the I-9301 and is the answer not in the manual?

Questions and answers

Summary of Contents for GST I-9301

  • Page 1 Insulation technology for input signal, good anti-interference ability. Cable checking. Plug-in structure. Description 548h/02 With a microprocessor, I-9301 Addressable Single I/O Module can communicate with fire alarm control panel B-9310 Back Box (FACP), check power cut, control output and LED. Conduit...
  • Page 2 Please contact your local distributor for products not covered by this warranty. The module is not used for gas extinguishing devices. This document is subject to change without notice. Please contact GST for more information or questions. GST China GST UK GST Dubai Gulf Security Technology Co., Ltd.

Table of Contents