GST DI-M9301 Quick Start Manual
GST DI-M9301 Quick Start Manual

GST DI-M9301 Quick Start Manual

Digital single input and output module

Advertisement

Quick Links

Features
Input port is provided with Class B pathway
supervision when connects with 4.7KΩ EOLR
(Part Number 3010786).
Input port can be programmed to monitor either
normally open or normally closed dry contact
input.
Input
can
also
"self-answering", which means that the Input port
monitoring is disabled, and the module will
directly send a "status" signal to FACP when the
dry-contact output changes state.
Addressable unit. Address can be programmed
in field.
Input port utilizes AD sampling technology for
precise testing.
Compatible with GST-M200 and GST-IFP4M Fire
Alarm Control Panels (FACP).
Guide rail for easy installation.
Standard: UL864, NFPA [70, 72].
Description
With a microprocessor, DI-M9301 Digital Single Input
and Output Module can communicate with fire alarm
control panel (FACP). On receiving start command
from the FACP, it will close the output relay and
illuminate the Active indicator.
Connection and Cabling
Terminals of the module are shown in Fig. 1.
Fig. 1
(Z1, Z2) IN & OUT: Connecting with the Signaling
Line Circuit (SLC) loop of FACP, polarity
insensitive.
I, G: Connecting with normally open dry contact
of an input device that closes when the device is
in alarm or changes state. It may also be set to
normally closed input by hand held programmer.
COM, NO, NC: Dry contact output terminals
CODE: Connecting with the programmer.
Recommended Wiring: minimum 17 AWG. Subject to
local codes.
30310199
Digital Single Input and Output Module
be
programmed
as
.
DI-M9301
Installation
Warning:
Before installing the module, disconnect power
from the loop.
1)
Before installation, make sure the enclosure is in
good condition and markings are complete.
2)
The module shall either be installed in a North
America standard metal electrical box. Minimum
size is 4 in. square, 2-1/8 in depth (in this case,
standard box cover is required), or in a UL
Signaling
Listed
minimum wiring entries and spacing as shown on
Fig 2 and Fig 3. Minimum mounting space is
67×40.5mm.
Fig 2
enclosure
that
provides
Issue 1.06
Fire Alarm
Equipment
47AU

Advertisement

loading
Need help?

Need help?

Do you have a question about the DI-M9301 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for GST DI-M9301

  • Page 1 With a microprocessor, DI-M9301 Digital Single Input Fig 2 and Fig 3. Minimum mounting space is and Output Module can communicate with fire alarm 67×40.5mm. control panel (FACP). On receiving start command from the FACP, it will close the output relay and illuminate the Active indicator.
  • Page 2 Fig. 6(line detection is provided by the controlled device).  Connection of the module to devices controlled by 24VDC is shown in Fig.7 (line detection is provided by the controlled equipment). Fig. 4 DI-M9301 DI-M9301 Control Control 4.7kΩ Input 4.7kΩ...
  • Page 3 Weight About 66.5g (with base) This Data Sheet is subject to change without notice. Please contact GST for more information or questions. Gulf Security Technology Co., Ltd. No. 80, Changjiang East Road, QETDZ, Qinhuangdao, Hebei, P. R. China 066004 Tel: +86 (0) 335 8502434 Fax: +86 (0) 335 8502532 service.gst@fs.utc.com www.gst.com.cn...