How Do I Set Reference Between Local And Remote Units - JDS Uniphase Certifier40G Manual

Cable certification tester
Table of Contents

Advertisement

Using the Certifier40G
2.1.7 How do I set reference between local and
remote units?
It is recommended that whenever the local and remote unit
pair is being used for the first time you perform a set
reference measurement. If there is a mismatch between the
software versions or the reference calibration between local
and remote units has expired, the Certifier40G would require
you to perform a set reference measurement.
To perform a set reference measurement, go to the TOOLS
menu and select the set reference measurement icon.
Connect the Certifier40G local and remote unit for reference
calibration. This is done by connecting a Permanent Link
Adapter at the local end and a Channel Adapter at the
remote end and connecting them together. Press " " to start
the Set Reference procedure, once the Set Reference is
complete the screen shows a Pass or Fail message. The
flow of the screens is shown below.
Figure 17: Screens showing Set Reference Procedure