Step 5 — Make Electrical Connections
WARNING
Electrical shock can cause personal injury and death. Shut off
all power to this equipment during installation. There may be
more than one disconnect switch. Tag all disconnect locations
to alert others not to restore power until work is completed.
CONNECTION TYPE
UNIT SIZES
FUSED DISCONNECT
NOTES:
1. Field wiring for supply conductors must be rated 75°C minimum.
2. Use copper conductors only.
Fig. 27 — 09FC 040 Pressure Curve
Table 4 — Field Wire Sizes
VOLTAGE
020
All
030
380-575V
040
380-575V
050
440-575V
060
575V
030
200/230V
040
200/230V
050
380-415V
060
380-460V
070
All
080
All
GPM

POWER SUPPLY

Electrical characteristics of available power supply must agree
with unit nameplate rating. Field wiring size must be within limits
shown in Table 4. See Table 5 for unit electrical data. See Fig. 28
and 29 for typical wiring connections.
IMPORTANT: Operating unit on improper supply voltage
or with excessive phase imbalance constitutes abuse and
may affect Carrier warranty.
MCA RANGE
WIRE SIZE RANGE
Up to 60A
#4 - #18
Over 60A
#1 - #8
24
MAXIMUM
NUMBER OF
LUG TORQUE
WIRES PER
PHASE
30 in-lb
1
(3.39 N-m)
40 in-lb
(4.52 N-m)
1