Communication - BACnet

See Table 15 for a list of BACnet Points.
Addressing the controller may be done with or without power.
Each time power is applied the controller reads the address.
Address is set using rotary switches. Set the Tens (10's) switch to
the tens digit of the address, and the Ones (1's) switch to the ones
digit. See Fig. 39.
Example: If the controllers address is 25, point the arrow on the
Tens (10's) switch to 2 and the arrow on the Ones (1's) switch to 5.
The factory default setting is 00 and must be changed to success-
fully install BACnet communication.
See Table 16 for required BACnet configurations.
p
POINT NAME
Fan VFD Speed Output
Mixing Valve Postion
Outdoor Air Temperature
Entering Load Water Temp
Leaving Load Water Temp
System Outdoor Air Temp
System Entering Load Water Temp
System Leaving Load Water Temp
System Control Setpoint
Chilled Water Setpoint
Chilled Water Supply Temp
Chilled Water Supply Setpoint
Cooling Lockout Offset
Cooling Lockout Temperature
Power Fail Restart Delay
Fan Minimum Speed
System OAT Master
Cool Enable
Bypass Valve Position
Fan VFD Enable
Occupancy Status
Operating Mode
Run Command
Shutdown
BAS On / Off
Low Chilled Water Supply Temp
Non-Operational Component
Reverse Load Water Flow
Outdoor Air Temp Sensor
Outdoor Air Temperature
Fan VFD Fail
Entering Load Water Temperature
Entering Load Water Temp Sensor
Leaving Load Water Temperature
Leaving Load Water Temp Sensor
Equipment Alarm
Table 15 — BACnet Points
TYPE
BACNET NAME
BAV
fanspeed
BAV
mixing_valve_pct
BAV
oa_temp
BAV
ent_load_wtr_temp
BAV
lvg_load_wtr_temp
BAV
system_oat
BAV
system_elwt
BAV
system_llwt
BAV
system_ctrl_stpt
BAV
ctrl_stpt
BAV
ctrl_temp
BAV
chws_setpoint
BAV
oat_cl_lockout_offset
BAV
oat_cl_lockout
BAV
start_delay
BAV
fan_min_speed
BAV
mstr_oa_temp
BBV
cl_enable
BBV
vlv_pos
BBV
fanenable
BBV
occ_status
BBV
op_mode
BBV
run_cmnd
BBV
shutdown
BMSV
keypad_ovrde
BBV
chws_lo_alarm
BBV
nonop_comp_alarm
BBV
reverse_flow_alarm
BBV
oat_fail
BBV
oat_alarm
BBV
fan_vfd_fail
BBV
elwt_alarm
BBV
ent_lwt_fail
BBV
llwt_alarm
BBV
lvg_lwt_fail
BBV
equip_alarm
51
Fig. 39 — Addressing the Controller
OBJECT ID
R/W
1001
R
1002
R
1003
R
1019
R
1020
R
1901
R/W
1910
R/W
1912
R/W
1916
R/W
2024
R
2035
R
3024
R/W
3027
R/W
9002
R/W
9007
R/W
0 - 600 sec
9009
R/W
80001
R
1011
R/W
2001
R
2004
R
2008
R
2014
R
1=Free Cool
2030
R
9001
R/W
1001
R/W
2=Occupied
3=Unoccupied
7021
R
7023
R
7025
R
7029
R
7036
R
7039
R
7040
R
7041
R
7043
R
7044
R
7048
R
RANGE
DEFAULT
0 - 100 %
0 - 100 %
°F
°F
°F
-999
-999
-999
-999
°F
°F
15 - 75 °F
44
1 - 10 °^F
3
-20 - 80 °F
50
20
0 - 100 %
20
°F
0=Disable
1
1=Enable
0=Close
1=Open
0=Stop
1=Start
0=Unocc
1=Occ
0=Bypass
0=Stop
1=Start
0=Inactive
0
1=Active
1=Inactive
1
0=Normal
1=Alarm
0=Normal
1=Alarm
0=Normal
1=Alarm
0=Normal
1=Alarm
0=Normal
1=Alarm
0=Normal
1=Alarm
0=Normal
1=Alarm
0=Normal
1=Alarm
0=Normal
1=Alarm
0=Normal
1=Alarm
0=Normal
1=Alarm