INSTALLATION
50E
BA.BB.BC03
4
WITH PLENUM
NOTESi
1.
MOTOR AT LEFT END OF UNIT FOR VERTICAL AIR DISCHARGE.
2.
MOTOR AT RIGHT
END OF UNIT FOR HORIZONTAL AIR DISCHARGE.
3.
CLEARANCE OF TWO FEET MUST BE LEFT AT EITHER SIDE OR FRONT OF
UNIT FOR FILTER REMOVAL.
4.
CLEARANCE MUST
BE LEFT AT LEFT END OF UNIT FOR T.X.V.
SERVICING AND AT RIGHT END FOR ELECTRICAL BOX
(CONTROL CENTER).
5.
END PANELS ON COMPRESSOR SECTION ARE REMOVABLE,
BUT NOT ON FAN
OR COIL SECTION.
6.
OUTSIDE AIR CAN BE TAKEN THROUGH COMPRESSOR SECTION THROUGH
REAR OF UNIT.
OPENING MUST
BE CUT
IN REAR COMPRESSOR SECTION
PANEL AND BAFFLE
®
MUST BE REMOVEO.
SEE FIG.
HORIZONTAL FAN DISCHARGE
WITH ACCESSORY PANELS
FIG. 11 - POSSIBLE FAN ARRANGEMENTS
RECOMMENDED ISOLATORS
A.
Sponge Rubber
B.
Corrugated Rubber Matting
C.
Fiberglas
Roof Insulation
8. INSTALL FILTERS
High velocity, cleanable type filters must be used.
One inch high velocity filters are shipped with the
unit; however, two inch filters may be used by re¬
moving the filter spacer channels from the filter
frame tracks,
TABLE 5 - FILTER SIZES
Model
Size (In.)
No. Required
50BA, BB,
1 x 20 x 25
3
BC024
1 x 16 x 25
3
To remove the filters, remove either of the side
filter access panels.
Filters may also be removed
through the front of the unit by loosening the two
wing nuts holding the sliding filter retainer in place,
sliding retainer up or down and removing the filters.
See Fig. 3, 4, 5, and 6.
9. MAKE AIR DUCT CONNECTIONS
DISCHARGE CONNECTIONS
Connect the flanged discharge openings to the supply
duct utilizing a canvas connection to prevent vibra¬
tion.
It is important that this connection be properh
fabricated to prevent high friction losses and air
noise.
RETURN CONNECTIONS
The return and outside air connections should be
brought to the filter rack through a canvas connectio
to prevent transmission of unit vibration.
When a duct blocks off the access panel provide a
slip joint in the duct work so that it may be removed
for service purposes.
OUTSIDE AIR INLET CONNECTIONS
Outside air inlet connections should be tapped into tl
return air duct work.
A damper must be provided ii
the outside air duct to permit the control of the out¬
side air volume.
10. INSTALL WATER CONNECTIONS
RECIRCULATING WATER SYSTEM
The 50BA and BC024 unit condensers are installed
9