Power Wiring - Carrier 09FC020 Installation, Start-Up And Maintenance Instructions

Table of Contents

Advertisement

LEGEND
AO
Analog Output (0-10 Vdc)
ALM
Alarm Relay
BO
Digital Output (Relay, 1A Max)
BMS
Building Management System
CB
Circuit Breaker
EWT
Entering Water Temperature
FU
Fuse
FM
Fan Motor
GND
Ground
IN
Thermistor or Dry Contact Input
LWT
Leaving Water Temperature
OAT
Outdoor Air Temperature
R1
CW Valve Relay
R2
CCW Valve Relay
R3
FC Enable Relay
R4
VFD Enable Relay
SW
Switch
TB
Terminal Block
TRAN —
Transformer
VFD
Variable Frequency Drive

POWER WIRING

All power wiring must comply with applicable local and national
codes. A fused disconnect is supplied in the control panel with an
external handle on all 09FC models.
General Wiring Notes:
1.
The control circuit does NOT require a separate power
source. Control circuit power is obtained by a step-down
transformer from the main three-phase power supply. The
LVT (low voltage terminal) strip is provided for field-wired
control devices.
Fig. 29 — Typical Main Power Connections
27
POWER
2.
All field power enters the unit through a hole located in the
bottom of the control box shelf. Refer to Fig. 25 for field wir-
ing details. Refer to Fig. 5-11 for exact location of field power
entry. Be sure to seal entering power wire conduit per NEC
requirements.
3.
Maximum field wire sizes allowed by lugs on fused discon-
nect are listed in Table 4.
4.
Terminals for field power supply are suitable for copper con-
ductors. Insulation must be rated 75°C minimum.
Control power is obtained from the main power supply and does
NOT require a separate source. A toggle switch, SW1 (marked