Table 18 — 5K Thermistor Temperature vs.
Resistance (cont)
°F
181
183
185
187
189
190
192
194
196
198
199
201
203
205
207
208
210
212
214
216
217
219
221
223
225
226
228
230
232
234
235
237
239
241
If a more accurate check is required, unit must be shut down and
thermistor removed and checked at a known temperature (freezing
point or boiling point of water) using either voltage drop measured
across thermistor at the J3 terminal, by determining the resistance
with unit shut down and thermistor disconnected from J3. Com-
pare the values determined with the value read by the control in
the Temperatures mode using the controller display.
°C
RESISTANCE, OHMS
83
570
84
552
85
535
86
518
87
502
88
487
89
472
90
458
91
444
92
431
93
418
94
405
95
393
96
382
97
370
98
360
99
349
100
339
101
329
102
320
103
311
104
302
105
293
106
285
107
277
108
269
109
262
110
255
111
248
112
241
113
234
114
228
115
222
116
216
Table 18 — 5K Thermistor Temperature vs.
Resistance (cont)
°F
243
244
246
248
250
252
253
255
257
259
261
262
264
266
268
270
271
273
275
277
279
280
282
284
286
288
289
291
293
295
297
298
300
302

Fan Blade and Fan Motor Service

A formed metal mount bolted to the coil caps supports each fan
and motor assembly. A shroud and a wire grille provide protection
from the rotating fan. See Figure 46. To remove the fan a special
puller (RCD part no. 30RB680082) can be used. The fan utilizes a
set screw and does not require the use of retaining compound in
the keyway. The fan can be removed without the puller, but its use
eases disassembly. The exposed end of the fan motor shaft is pro-
tected from weather by grease. If fan motor must be removed for
service or replacement, re-grease the fan shaft. The fan needs to be
positioned fully down against the step on the motor shaft. Apply
blue thread locker (Loctite 243) to the threads of both the axial bolt
and the set screw. Install the thick washer and M8 axial bolt; do
not fully tighten. Install set screw and tighten to 16 ± 2 ft-lbs (21.7
± 2.7 Nm). Torque the axial bolt to 24 ± 2 ft-lbs (32.5 ± 2.7 Nm).
Reinstall shroud and wire grille.
59
°C
RESISTANCE, OHMS
117
210
118
205
119
199
120
194
121
189
122
184
123
179
124
175
125
170
126
166
127
162
128
157
129
154
130
150
131
146
132
142
133
139
134
135
135
132
136
129
137
126
138
123
139
120
140
117
141
114
142
111
143
109
144
106
145
104
146
101
147
99
148
97
149
94
150
92