Securing of panels Installation of REC Alpha Series panels Mounting REC Alpha Series panels with continous rails parallel to short side of the panel Mounting REC Alpha Series panels with continous rails parallel to long side of the panel Mounting REC Alpha Series panels with short rails...
This does not apply to damages due to a panel fault, in cases of loss of life, bodily injury or damage to health or in the event of a grossly negligent breach of obligations on the part of REC SOLAR PTE. LTD. and/or in the event of an intentional or grossly negligent breach of obligations by a legal representative or vicarious agent.
SAFETY IN THE WORKING AREA Installation of REC solar panels may involve working on rooftops or raised platforms. Ensure all local regulations regarding working at heights and fall protection are followed. Before beginning work on an installation, ensure all working surfaces are structurally sound and capable of bearing the weight of employees and required equipment.
PANEL HANDLING In order to avoid damage, all REC solar panels should be handled with care and protected from damage at all times. All warnings and instructions on the packaging should be observed. Follow these guidelines when unpacking, transporting, carrying, installing or storing panels: •...
FIRE GUIDELINES The REC solar panels covered by this manual have a Class C (referencing UL 790) fire classification. The REC Alpha Series is rated Type 2 fire classification according to IEC 61730-2:2016 (ref. ANSI/UL 1703); The REC Alpha 72 XV Series is rated Type 1 fire classification according to IEC 61730-2:2016 (ref.
REC modules must be secured with a torque as shown in the table below (fig. 1). Clamp installation must be carried out according to the manufacturer’s instructions, including specific hardware and torque requirements. Ensure the clamps used are suitable for the planned installation and expected system design loads.
MOUNTING REC ALPHA SERIES PANELS WITH CONTINOUS RAILS PARALLEL TO SHORT SIDE OF THE PANEL A continous rail (or other support structure) spans the complete underside of the panel. Fig. 3: Clamping of REC Alpha Series panels with rails parallel to short side of the panel 27.4 in [695 mm] 27.4 in [695 mm]...
Page 9
MOUNTING REC ALPHA SERIES PANELS WITH CONTINOUS RAILS PARALLEL TO LONG SIDE OF THE PANEL A continous rail (or other support structure) spans the complete underside of the panel. Fig. 4: Clamping of REC Alpha Series panels with rails parallel to long side of the panel 25.6 in [650 mm] 25.6 in [650 mm]...
Once a module is secured in each of the 4 zones (fig. 2), additional clamps, i.e., ≥5, may be freely located on panel frame without affecting the warranty. Loads marked with a were not certified as part of IEC 61215 / UL 61730 testing; these have been evaluated by REC’s internal testing process.
MOUNTING REC ALPHA 72 SERIES PANELS WITH CONTINOUS RAILS PARALLEL TO SHORT SIDE OF THE PANEL A continous rail (or other support structure) spans the complete underside of the panel. Fig. 6: Clamping of REC Alpha 72 Series panels with rails parallel to short side of the panel 30.7 in [780 mm] 30.7 in [780 mm]...
Page 12
Once a module is secured in each of the 4 zones (fig. 2), additional clamps, i.e., ≥5, may be freely located on panel frame without affecting the warranty. Loads marked with a were not certified as part of IEC 61215/ UL 61730 testing; these have been evaluated by REC’s internal testing process.
MOUNTING METHODS: MOUNTING HOLES The REC solar panels covered by this manual can be installed utilizing the four mounting holes (11 x 6.6 mm) on the underside of the panel (fig. 8 & 9) in conjunction with a device, e.g., screws, lockbolts or structural blind fasteners, with specifications suitable for the installation (fig. 10).
DRAINAGE HOLES On the long and short sides of the REC frame small drainage holes can be found that allow humidity and water to exit the frame easily and minimize damage (fig. 12). These are spaced 55 mm from the corner on 60-cell format panels and 60 mm on 72-cell format panels. These holes must not be used for mounting the panel, and they must not be covered by any part of the mounting structure.
CONNECTIONS AND CONNECTORS The connector type(s) used on REC panels are indicated in the product specifications at the rear of this manual. The connector IP rating is only valid when correctly connected. All connectors and cables must be secure and tight as well as electrically and mechanically sound. UV-resistant cables and connectors approved for outdoor use must be used.
DISPOSAL OF OLD ELECTRICAL AND ELECTRONIC EQUIPMENT Panels should be recycled at the end of their useful life according to local guidelines and regulations. By ensuring REC solar panels are disposed of correctly, you will help prevent potential negative consequences for the environment and human health which could otherwise be caused by inappropriate waste treatment.
, REC Group is an international pioneering solar energy company dedicated to empowering consumers with clean, aff ordable solar power. As Solar’s Most Trusted, REC is commi ed to high quality, www.recgroup.com innovation, and a low carbon footprint in the solar materials and solar panels it manufactures.
, REC Group is an international pioneering solar energy company dedicated to empowering consumers with clean, aff ordable solar power. As Solar’s Most Trusted, REC is commi ed to high quality, www.recgroup.com innovation, and a low carbon footprint in the solar materials and solar panels it manufactures.
, REC Group is an international pioneering solar energy company dedicated to empowering consumers with clean, aff ordable solar power. As Solar’s Most Trusted, REC is commi ed to high quality, www.recgroup.com innovation, and a low carbon footprint in the solar materials and solar panels it manufactures.
INSTALLATION ENVIRONMENT Installation site • REC solar panels may only be installed on closed bodies of fresh water where water salinity does not exceed 15 PSU (25 mS/cm) at 77°F (25°C). This specifically excludes mounting on sea and ocean applications. •...
11.8 in (300 mm) boundary have to be reduced to 80 V or less within 30 seconds of rapid shutdown initiation. MLPE devices may be used on REC solar panels where desirable or mandatory (note that the certification testing of solar panels does not include testing with MLPE devices).
Addition of load specifications for different clearance gaps and rail lengths 09.2020 Added minimum required torque for clamping 12.2020 Addition of REC Alpha 72 Series 03.2021 Updated Datasheets REC Installation Manual - REC Alpha Panels - UL 61730 Rev F - 02.21 Ref: PM-IM-23...
Need help?