20 Operation principle and hardware description
X20
Customer Interface Terminal Block
1
3
PE
X200
Customer Interface Terminal Block
1
2
5
6
9
10
3
4
7
8
X210
Customer Interface Terminal Block
Forbid customer to set common point for open status, close status and ready status!
3
Internal supply: 230 VAC, 0.25A
4
1
Internal supply:24 VDC, 20mA
2
5
Internal supply:24 VDC, 20mA
6
X220
Customer Interface Terminal Block
1
2
3
4
5
6
11
Control Power Supply Failure
12
13
Space Heater Failure
14
Below lamp indicators can be found on front door for friendly operation:
QF1 close/open
QS1 close/open
QS2 close/open
QS3 close/open
VFD operation mode
Bypass operation mode
L
N
PE
Auxiliary contacts to
customer
Thermal current: Ith = 6 A
@40 °C
Rated operational current:
AC-15 240 VAC, 4 A; 400
VAC, 3 A; 500 VAC, 2A
DC-13 24 VDC, 2.5 A; 110
VDC, 0.7 A; 240 VDC, 0.4
A
MCB Close Status
MCB Open Status
MCB Ready Status
QS1 Close Status
QS2 Close Status
QS3 Close Status
Control power supply
230 VAC, 50/60 Hz, 3 A
Auxiliary contacts to customer
Thermal current: Ith = 6 A @40 °C
Rated operational current:
AC-15 240 VAC, 4 A; 400 VAC, 3 A; 500
VAC, 2A
DC-13 24 VDC, 2.5 A; 110 VDC, 0.7 A;
240 VDC, 0.4 A
MCB Close Status
MCB Open Status
MCB Ready Status
Auxiliary contacts to customer
380 VAC, 16 A; 250 VDC, 5 A
Connect contacts to customer
AC-14 400 VAC, 1 A; 230 VAC. 2 A
DC-12 220 VDC 1 A; 110 VDC 1.5 A
DC-13 60 VDC, 2 A; 24 VDC 4 A