6-4. Model: AOYG45KATA

NOTE: Values mentioned in the table are calculated based on the maximum capacity.
COOLING
Indoor unit is higher
than outdoor unit *1
Indoor unit is lower
than outdoor unit *2
HEATING
Indoor unit is higher
than outdoor unit *1
Indoor unit is lower
than outdoor unit *2
6-4. Model: AOYG45KATA
5
30
20
10
7.5
0.988
5
0.992
0.992
0
1.000
1.000
-5
1.000
1.000
-7.5
1.000
-10
-20
-30
5
30
20
10
7.5
1.000
5
1.000
1.000
0
1.000
1.000
-5
0.995
0.995
-7.5
0.993
-10
-20
-30
- 88 -
Pipe length (m)
7.5
10
0.973
0.977
0.981
0.989
0.989
0.989
0.989
Pipe length (m)
7.5
10
0.998
0.998
0.998
0.998
0.993
0.991
0.988
6. Capacity compensation rate for pipe length and height difference
20
30
0.900
0.937
0.915
0.952
0.931
0.956
0.934
0.960
0.938
0.967
0.945
0.967
0.945
0.967
0.945
0.967
0.945
0.967
0.945
0.945
20
30
0.978
0.988
0.978
0.988
0.978
0.988
0.978
0.988
0.978
0.988
0.978
0.983
0.973
0.981
0.971
0.978
0.968
0.968
0.958
0.949