  • Page 1 INSTALLATION MANUAL MANUAL DE INSTALACIÓN MANUEL D’INSTALLATION INSTALLAZIONE MANUALE INSTALLATIONSHANDBUCH Heat pump Heat recovery RVMH060GDM3 RVMR100GCM0 RVMH100GCM3 System Air Conditioner Sistema Acondicionador de aire Equipement pour air conditionné Sistema Area Condizionata System Klimaanlage E S F I D DB98-21729A(2)
  • Page 2 Type of outdoor unit Type A Type B Type C Design Heat RVMH060GDM3 RVMH100GCM3 pump Model Heat RVMR100GCM0 recovery R407C type outdoor unit...
  • Page 3: Table Of Contents

    Contents REPARING THE NSTALLATION Locating the Units ..................NSTALLING THE NITS Electrical Connections ................. Installing the Refrigerant Pipework ............. OMPLETING THE NSTALLATION AND OMMISSIONING Performing the Gas Leak Tests and Insulation of Pipework ....... Preparing and Charging the Refrigerant Pipework ........Installing MCU(Mode Change Unit) ............
  • Page 4 National Safety Precautions The following safety precautions must be taken when using your air conditioner. Risk of electric shock. • Can cause injury or death. • Disconnect all WARNING remote electric power supplies before servicing, installing or cleaning. • This must be done by the manufacturer or its service agent or a similar qualified person in order to avoid a hazard.
  • Page 5: Locating The Units

    Locating the Units You should observe the following restrictions when you decide the installation place. NEVER place the outdoor unit on its side or upside down. The compressor lubricating oil may run into the circuit and damage the outdoor unit compressor. Choose a dry and sunny place avoiding direct sunlight or strong winds.
  • Page 6 If you install several outdoor units simultaneously, observe the space for ventilation and free airflow. If the space for ventilation is insufficient, the air conditioner may be inefficient. SAMSUNG logo is attached on the front side of the outdoor unit. Installation space of Type A...
  • Page 7 When installing more than 1 outdoor unit Unit : mm When the air outlet is toward the wall 300 or more 600 or more 600 or more 600 or more When 3 sides of the outdoor unit are blocked by the wall 600 or more 600 or more When front and rear side of the outdoor unit is toward the wall...
  • Page 8 Locating the Units (Continued) Installation space of Type B, C Unit : mm Front side 300 or more or more or more or more When installing in a row Front side 300 or more or more or more or more Front side When installing in two rows Front side...
  • Page 9 When there is high obstacle near the outdoor unit (Installation space of Type B, C) Unit : mm If the outer wall is lower than the outdoor unit When installing in a row When installing in two rows When installing in three rows When installing the pipe horizontally from the front side of the outdoor unit, observe the space of 500mm or more between the outdoor unit and the pipe.
  • Page 10 Locating the Units (Continued) If the outer wall is higher than the outdoor unit When installing louvre When installing no louvre - Set the inlet fan speed less than 1.5m/s from the louvre. - Install the outdoor unit support of 500~1000mm high. - Set the height (HD) of the discharge duct H-h.
  • Page 11 Installing the Outdoor Unit When installing Type A outdoor unit Install the outdoor unit higher than 300mm from the base surface and install the drain hole to connect the pipe to the drainage. The concrete foundation should be 1.5 times larger than bottom of the outdoor unit.
  • Page 12 Locating the Units (Continued) When installing Type B, C outdoor unit Install the outdoor unit higher than 200mm from the base surface and install the drain hole to connect the pipe to the drainage. The concrete foundation should be 1.5 times larger than bottom of the outdoor unit.
  • Page 13 Example of the place of the base and shape of the anchor bolt Type A Anchor bolt hole Unit : mm Type B, C Anchor bolt hole Unit : mm To protect the internal components of the outdoor unit from small animals, secure the pipework entrance to the unit.
  • Page 14: Electrical Connections

    Electrical Connections All wiring and parts shall be the rated and sized accordingly. For details of wiring, refer to the circuit diagram attached on to the outdoor unit. The electric work should be performed by qualified electrical technicians. The circuit diagram for wiring shows only the concept and so the details for actual work is not described.
  • Page 15 Connection of the power cable (3 phase 4 wire) Power supply cable: 3 phase 380~415V Power supply cable: 1 phase 220-240V~ Signal cable: Communication cable/ Home server Distribution board Outdoor unit Indoor Unit Communication cable 1 phase 2 wire 3 phase 3 wire Earth wire 220-240V~/50Hz 380~415V/50Hz...
  • Page 16 Electrical Connections (Continued) Specification of electronic wire of the outdoor unit Power Supply Outdoor 3 Phase Single Phase unit Type Power Max/Min MCCB/ Power Power Max/Min MCCB/ Power Length Length Supply(V) cable Supply(V) cable 3.5mm, 18m or 380~ 220- 4 wires less 2.0 mm 415V/...
  • Page 17 Power Wiring Diagram You can use 3 phase 3 wires and single phase ELB with the outdoor unit or 3 phase 4 wires ELB separately. When using 3 phase and single phase ELB Power Supply MCCB Part B Part A Single 3 Phase Phase...
  • Page 18 Electrical Connections (Continued) Wiring Diagram of the indoor and outdoor unit Indoor Unit 1 Indoor Unit 2 Indoor Unit 3 Outdoor Unit When the communication cable exceeds the specified length, the air conditioner may not operate due to the trouble of communication between indoor and outdoor unit.
  • Page 19 Power wiring and communication wiring configuration Be sure to run the power supply cable and the communication cable through the electrical conduit as seen in the picture. Install the communication cable, indoor power cable and the main power cable in the cable tube. Communication cable Indoor power...
  • Page 20: Installing The Refrigerant Pipework

    Type Outdoor unit length of pipe difference of Low pressure High pressure Liquid pipe height(m) gas pipe gas pipe Ø 9.52 Ø 22.23 RVMH060GDM3 30(25) (3/8) (7/8) Heat Pump Ø 12.70 Ø 28.58 50(40) RVMH100GCM3 (1/2) Heat Ø 12.70 Ø 28.58 Ø...
  • Page 21 Selecting the refrigerant pipe and the allowable length of the pipe The refrigerant pipe should be short as much as possible and minimize the maximum allowable difference of height. When installing 6 indoor units using only the refnet joint (Outdoor unit Type A, B) Outdoor unit A, B, C, D, E: Refnet joint (When selecting the refnet joint B:Total capacity of the indoor unit 2, 3, 4, 5, 6)
  • Page 22 Installing the Refrigerant Pipework (Continued) When installing 6 indoor units using distributor kit(Outdoor unit Type A, B) Outdoor unit Distributor kit A, B, C: Refnet joint (When selecting the refnet joint B:Total capacity of the indoor unit 2, 3, 4, 5, 6) Outdoor unit Type A Type B...
  • Page 23 When installing 8 indoor units using branch pipe and MCU(Outdoor unit Type C) Outdoor unit Outdoor unit Type C Section Total length of pipe (m) Maximum allowable The distance between length of Actual length the outdoor unit and pipe For example) a + c + k ≤ 100m the furthest indoor unit Difference of height between the 50(40)
  • Page 24 Installing the Refrigerant Pipework (Continued) Selecting the size of the refrigerant pipe after the first refnet joint Outdoor unit Type A, B (1/2) 16,000W or more Ø 12.70 t0.8 Total capacity Liquid pipe of the indoor (3/8) 4,700W ~ 16,000W or less Ø...
  • Page 25 Cutting or Extending the Pipe Always utilize the correct tools. (pipe cutter, reamer, flaring tool and pipe holder) If you want to shorten the pipe, cut it using a pipe cutter ensuring that the cut edge remains at 90° with the side of the pipe. There are some examples of correctly and incorrectly cut edges below.
  • Page 26 Installing the Refrigerant Pipework (Continued) Selecting the Refnet Joint Selecting the first refnet joint Select the refnet joint separately for connecting the indoor and outdoor unit. Select the first refnet joint model from the outdoor unit referring to the table below. Length Diameter Refnet joint...
  • Page 27 Installing the Refnet Joint Install the refnet joint ‘horizontally’ or ‘vertically’. Horizontal joint Vertical joint Install the refnet joint maintaining ±15° start from the horizontal line. When installing the refnet joint, do not bend the main pipe in the connection part. If it is unavoidably bent, install the refnet joint horizontally and the length is to be more than 500mm from the connection part to the main part.
  • Page 28: Performing The Gas Leak Tests And Insulation Of Pipework

    Performing the Gas Leak Tests and Insulation of Pipework You must check if there is a gas leak before completing all the installation process. Insulating the refrigerant pipe Be sure to insulate the refrigerant pipe, joint and connection part. Insulator - If you insulate the pipes, the condensed water does not fall from the pipes and the capacity of the air conditioner is improved.
  • Page 29 Selecting the insulator of the refrigerant pipe Insulate the gas side and liquid side pipe referring to the thickness according to the pipe size. The thickness according to the pipe size is a standard of the indoor temperature of 27°C and humidity of 80%. If installing in an unfavorable conditions from it, use thicker one.
  • Page 30: Preparing And Charging The Refrigerant Pipework

    Preparing and Charging the Refrigerant Pipework Performing the Refrigerant Gas Leak Test Service port Gas side stop valve (All closed) Indoor unit Outdoor unit Refnet joint Gas pipe Flange Flange Flaring connection part connection or Brazing part brazed part Service port Flaring Gauge holder connection part...
  • Page 31 Vacuum Drying with the Vacuum Pump To remove moisture inside of the pipe, perform vacuum drying after test of gas leak. Gas side stop valve (All closed) Outdoor unit Gas pipe Service port Liquid side pipe Gauge holder Liquid side stop High valve(All closed) pressure...
  • Page 32 Apply the rear side of the distributor kit refrigerant 0.01kg per meter when using MXD- and MCU-4ECEV. The amount of basic charging for pipes Model of the Factory charged Basic charging for Type outdoor unit (kg) pipes (kg) RVMH060GDM3 Heat pump RVMH100GCM3 14.0 Heat recovery RVMR100GCM0 17.0...
  • Page 33: Installing Mcu(Mode Change Unit)

    Installing MCU (Mode Change Unit) You must install MCU when using Type C outdoor unit. Model of MCU Install appropriate MCU according to the specification and the number of the indoor unit. Model Type Remarks MCU that the EEV is not included: MCU-6ECE 6 indoor units can be connected.
  • Page 34 Installing MCU (Continued) Preparation before installing MCU Check the size of the MCU and installation place. Concrete Anchor hole Insert Check the condition of installation. Determine the position to install the MCU. Make a hole at the ceiling and maintain space between MCU and ceiling. Bolt for fixing the ceiling To prevent vibration, you may have to strengthen the ceiling.
  • Page 35 Fixing MCU and Connecting the Refrigerant Pipe Install the MCU using bolts. Use hole-in anchor to strengthen the ceiling for sustain the weight of the indoor unit in case of existing ceiling. Use the sunken insert, sunken anchor or accessory purchased in the market incase of new ceiling.
  • Page 36 Installing MCU (Continued) Insulating pipes and Connecting the Drain Hose Connecting the drain pipe Connect the drain pipe to the connection part. - The connection port and PVC drain pipe must be fixed with PVC adhesive. Ø Ø - PVC drain pipe: VP25(Inside diameter: 25, Outside diameter: Set the gradient of the drain pipe more than 1/100 and insulate the drain pipe.
  • Page 37 Connecting Electronic Wires and Setting Address Power and Power cable Communication communication from cable from cable for outdoor unit outdoor unit indoor unit Connecting the Power and Communication Cable Connect the 220V power cable from the outdoor unit to L, N of MCU. Connect the communication cable from the outdoor unit to F1, F2 of MCU.
  • Page 38 Installing MCU (Continued) Setting MCU Address DIP switch for indoor unit setting (ON:Use, OFF:Not use) Rotary switch for indoor unit address Rotary switch for MCU address Set the rotary switch for the indoor unit address of MCU same as the indoor unit address of pipe of the indoor unit MCU.
  • Page 39: Setting The Option Switch And Function Of The Key

    Setting the Option Switch and Function of the Key Setting the Option Switch Setting part of the outdoor unit PCB Type A Setting switch of number of the indoor unit Type B Setting switch of number of the indoor unit Type C Setting switch of number of the...
  • Page 40 Setting the Option Switch and Function of the Key (Continued) Setting switch of number of the indoor unit Number of the indoor 10 11 12 13 14 15 16 unit Number of the switch For example: Set the switch to ‘3’ if 3 indoor units are installed. The way of displaying number and alphabet of the PCB display.
  • Page 41 Key function of the outdoor unit PCB Outdoor unit Type A, B Check mode RESET View mode Function of KEY Function KEY 1 KEY 2 KEY 3 KEY 4 Number of (Displayed on SEG 3, 4) (Displayed on SEG 3, 4) (Displayed on SEG 3, 4) (Displayed on SEG 3, 4) press times...
  • Page 42 Setting the Option Switch and Function of the Key (Continued) Outdoor unit Type C Check mode RESET View Piping mode check Function of KEY Function KEY 1 KEY 2 KEY 3 KEY 4 Number of (Displayed on (Displayed on (Displayed on (Displayed on KEY 5 press times...
  • Page 43 Memo...
  • Page 44 THIS AIR CONDITIONER IS MANUFACTURED BY: ESTE AIRE ACONDICIONADO HA SIDO FABRICADO POR: CE CLIMATISEUR EST FABRIQUE PAR: QUESTO CONDIZIONATORE D’ARIA È PRODOTTO DA : DIESE KLIMAANLAGE IST FABRIZIERT VON: ELECTRONICS Printed in Korea...