Schmalz ECBPMi UR Operating Instructions Manual page 29

Electrical vacuum generator
Table of Contents

Advertisement

Vacuum
[mbar]
H1-h1
The specified value for the max. permitted evacuation time t1 can be set using the IO-Link ("Permissible
evacuation time" parameter) [0x006B]. Setting the value to "0" (= off) deactivates monitoring. The maxi-
mum permitted evacuation time setting is 9.99 s.
   Measuring the Evacuation Time t0 and t1
Measuring the evacuation time t0:
The time is measured (in ms) from the beginning of the suction cycle to the time when the limit value H2
is reached ("Evacuation time t0" parameter [0x0094]).
Measuring the evacuation time t1:
The interval between reaching the limit values H2 and H1 is measured (in ms) ("Evacuation time t1" pa-
rameter [0x0095]).
   Leakage Monitoring and Evaluation
The leakage is measured and monitored in control mode. The measurement is performed using a calcula-
tion based on the pump control values (speed and duration) when readjusting to the setpoint H1. The cal-
culated value can be read as a volume flow rate using the "Leakage rate" parameter [0x00A0] or alterna-
tively using the process data (EPC-Select) in ml/min.
Evaluation of the leakage level differentiates between two statuses:
Leakage L < permitted value -L-
If the leakage L is less than the set value "Permissible leakage rate"
The condition monitoring warning is not activated
There is no effect on the system status light and the display on the LED ring
Leakage L > permitted value -L-
If the leakage L is greater than the set value "Permissible leakage rate"
The condition monitoring warning is activated
The system status light switches to yellow and a warning (orange) is displayed on the LED ring
EN-US · 30.30.01.02196 · 01 · 11/20
Start suction cycle
Description of Functions
Time [s]
29 / 56