Electromagnetic compatibility:
EMC emitted interference
Conducted interference / due to burst / acc. to IEC 61000-4-4
Conducted interference / due to surge / acc. to IEC 61000-4-5
Conducted interference / due to high-frequency radiation / acc. to IEC
61000-4-6
Field-bound parasitic coupling / acc. to IEC 61000-4-3
Electrostatic discharge / acc. to IEC 61000-4-2
Overvoltage category
Ambient conditions:
Ambient temperature
during operation
during storage
during transport
Air pressure
during operation
during storage
Degree of pollution
Installation altitude / at height above sea level / maximum
Relative humidity
at 25 °C / during operation / maximum
at 50 °C / during operation / maximum
at 50 °C / during operation / maximum / Note
SIPLUS HCS4200
Operating Instructions, 11/2015, A5E35066204A/RS-AA/002
Technical specifications
13.4 Technical specifications for I/O module
Limit value in accordance with IEC 61000-6-
4:2007 + A1:2011
2 kV signal cables
not applicable
10 V (0.15 ... 80 MHz)
10 V/m (80 ... 1000 MHz), 3 V/m (1.4 ... 2.0
GHz), 1 V/m (2.0 ... 2.7 GHz)
4 kV contact discharge / 8 kV air discharge
III
0 ... 55 °C
-25 ... +70 °C
-25 ... +70 °C
860 ... 1 080 hPa
660 ... 1 080 hPa
2
2 000 m
95 %
50 %
95% at 25°C, decreasing linearly down to 50%
at 50°C