Lennox FLEXY FX 025 Application Manual page 40

Rooftop packaged unit with heat recovery
Table of Contents

Advertisement

ELECTRICAL DATA
MODBUS - BACNET
10 = 1.0
29H
41
R
g/Kg
2AH
42
R
1 = 1 pa
2BH
43
R
1 = 1 ppm
2CH
44
R
1 = 1%
2DH
45
R
1 = 1%
2EH
46
R
1 = 1%
2FH
47
R
1 = 1%
30H
48
R
1 = 1%
31H
49
R
10 = 1.0°c
32H
50
R
10 = 1.0°c
33H
51
R
10 = 1.0°c
34H
52
R
10 = 1.0°c
35H
53
R
10 = 1.0%
36H
54
R
10 = 1.0%
37H
55
R
10 = 1.0%
38H
56
R
10 = 1.0%
39H
57
R
1 = 1 h
3AH
58
R
1 = 1 h
3BH
59
R
1 = 1 h
3CH
60
R
1 = 1 h
3DH
61
R
1 = 1 h
3EH
62
R
bit
3FH
63
R
bit
40H
64
R
40H
64
R
• 38 •
[Absolute Humidity] Outdoor
[Flow] Differential pressure on the air, in pascal
[CO²] Level in ppm
[% of opening] Register of fresh air
[% of opening] Valve gas
[% of opening] Electrical heaters (Triac)
[% of opening] Hot water coil
[% of opening] Humidifi er
[Dry contact] Temperature, Free 1, BE50-J9-B1
[Dry contact] Temperature, Free 2, BE50-J9-B2
[Dry contact] Temperature, Free 3, BE50-J10-B3
[Dry contact] Temperature, Free 4, BE50-J10-B4
[Dry contact] Humidity, Free 1, BE50-J9-B1
[Dry contact] Humidity, Free 2, BE50-J9-B2
[Dry contact] Humidity, Free 3, BE50-J10-B3
[Dry contact] Humidity, Free 4, BE50-J10-B4
[Running Time, Count] Fan, Blower
[Running Time, Count] Compressor, 1
[Running Time, Count] Compressor, 2
[Running Time, Count] Compressor, 3
[Running Time, Count] Compressor, 4
[Alarm]
bit.0 = Air Flow
bit.1 = Dirty Filters
bit.2 = No Filters
bit.3 = Electrical heaters
bit.4 = High Temperature, Supply
bit.5 = Low Temperature, Room
bit.6 = Gas Burner 1
bit.7 = Gas Burner 2
bit.8 = Low Temperature, Supply
bit.9 = High Temperature, Room
bit.10 = Humidifi er
bit.11 = Low Humidity, Room
bit.12 = High Humidity, Room
bit.13 = Pump
bit.14 = Real Time Clock
bit.15 = BE50
[Alarm]
bit.0 = Probes & Sensors
bit.1 = Fan, Blower
bit.2 = Low Temperature, Condenser Water
bit.3 = High Temperature, Condenser Water
bit.4 = Flow Switch, Condenser Water
bit.5 = Smoke Detector
bit.6 = Fans, Condenser
bit.7 = Compressor 1, H.P. & I.P.
bit.8 = Compressor 1, L.P.
bit.9 = Compressor 2, H.P. & I.P.
bit.10 = Compressor 2, L.P.
bit.11 = Compressor 3, H.P. & I.P.
bit.12 = Compressor 3, L.P.
bit.13 = Compressor 4, H.P. & I.P.
bit.14 = Compressor 4, L.P.
bit.15 =
not used
CONTROL variables
Application Guide • FLEXY FX-AGU-1112-E
2121
2123
2131
2132
2413
2618
2627
2633
2714
2161
2162
2163
2164
2165
2166
2167
2168
2318
2519
2529
2539
2549
...
...

Hide quick links:

Advertisement

Table of Contents