PERFORMANCES
SIZE
025
030
035
040
055
070
085
100
110
140
170
• 18 •
- ELECTRIC HEATER CAPACITIES
Available capacity
kW
9
18
9
18
18
36
18
36
18
36
36
72
36
72
36
72
36
72
36
72
36
72
Number of stages
Full modulation
Full modulation
Full modulation
Full modulation
Full modulation
Full modulation
Full modulation
Full modulation
Full modulation
Full modulation
Full modulation
Temperature rise at nominal air fl ow
50%
3,4°C
6,8°C
3,4°C
6,8°C
4,5°C
9,0°C
3,8°C
7,5°C
3,0°C
6,0°C
5,0°C
10,0°C
4,0°C
8,0°C
3,1°C
6,3°C
2,8°C
5,7°C
2,3°C
4,5°C
2,0°C
4,0°C
Application Guide • FLEXY FX-AGU-1112-E
100%
6,8°C
13,5°C
6,8°C
13,5°C
9,0°C
18,0°C
7,5°C
15,0°C
6,0°C
12,0°C
10,0°C
20,0°C
8,0°C
16,0°C
6,3°C
12,5°C
5,7°C
11,4°C
4,5°C
9,0°C
4,0°C
8,0°C