Control Variables - Lennox FLEXY FX 025 Application Manual

Rooftop packaged unit with heat recovery
Table of Contents

Advertisement

ELECTRICAL DATA
MODBUS - BACNET
@
@
(hexa)
(deci)
01H
1
R/W
02H
2
R/W
03H
3
R/W
04H
4
R/W
05H
5
R/W
06H
6
R/W
07H
7
R/W
08H
8
R/W
09H
9
R/W
0AH
10
R/W
0BH
11
R/W
0CH
12
R/W
0DH
13
R/W
0EH
14
R/W
0FH
15
R/W
10H
16
R/W
11H
17
R/W
12H
18
R/W
13H
19
R/W
14H
20
R/W
15H
21
R/W
16H
22
R/W
17H
23
R/W
18H
24
R/W
19H
25
R/W
1AH
26
R/W
1BH
27
R/W
1CH
28
R/W
1DH
29
R/W
1EH
30
R/W
1FH
31
R/W
20H
32
R/W
21H
33
R
22H
34
R
23H
35
R
24H
36
R
25H
37
R
26H
38
R
27H
39
R
28H
40
R
Application Guide • FLEXY FX-AGU-1112-E
L
[On / Off] Unit
L
[Reset] Discharges the safety measures of the unit
L
[Enable] Stopping and running of the Fan Blower.[Off] the blower is stopped, [On] the
blower is running.
L
[Enable] Stopping and running of the fan in the «Control Dead Zone». [Off] the blower is
stopped, [On] the blower is running.
L
[BMS] Activation of the Inoccupation mode [Off] occupation mode - [On] inoccupation
mode
L
[Room regulation] Choices of the priority of regulation in Heating - [Off] Heat Pump then
Hot water coil or Electric or Gas [On] Hot water coil or Electric or Gas then Heat Pump
L
[F-Air Reheat] Activate reheating of the fresh air in the dead zone to maintain supply
temperature.
L
[F-Air Reheat] Choices of the priority of regulation in Heating - [Off] Heat Pump then Hot
water coil or Electric or Gas [On] Hot water coil or Electric or Gas then Heat Pump
L
[Enable] Run eco: [On] the Economiser is running, [Off] the Economiser if stopped.
L
[Enable] Run CO2 Sensor: [On] Switch-on the CO2 control on a Zone, [Off] Stop the
CO2 control on a zone.
L
[Enable] [OFF] Force the unloading of compressors in cooling mode.
L
[Enable] [OFF] Force the unloading of compressors in heating mode.
L
[Enable] [OFF] Force the unloading of heating module (electric, gas or heat water coil)
L
[Enable] [OFF] Force the unloading of humidity control.
L
not used
L
[Clock] [OFF] read hour & minute [ON] write hour & minute
L
[Dry contact] Digital Output, Free 1, BM50-J17-NO12
L
[Dry contact] Digital Output, Free 2, BE50-J5-NO1
L
[Dry contact] Digital Output, Free 3, BE50-J6-NO2
L
[Dry contact] Digital Output, Free 4, BE50-J7-NO3
L
[Dry contact] Digital Output, Free 5, BE50-J8-NO4
L
not used
L
not used
L
not used
L
not used
L
not used
L
not used
L
not used
L
not used
L
not used
L
not used
L
not used
L
[Alarm] General
L
[On/Off] Fan, Blower
L
[On/Off] Fan, Extraction
L
[On/Off] Compressor, 1
L
[On/Off] Compressor, Heat pump, 1
L
[On/Off] Compressor, 2
L
[On/Off] Compressor, Heat pump, 2
L
[On/Off] Compressor, 3

CONTROL variables

DS50
3111
3112
3351 (BMS)
3352 (BMS)
3935
3324 (BMS)
3331 (BMS)
3332 (BMS)
3353 (BMS)
3354 (BMS)
3355 (BMS)
3356 (BMS)
3357 (BMS)
3358 (BMS)
...
2141
2142
2143
2144
2145
1000
2315
2321
2516
2517
2526
2527
2536
• 35 •